User Manual

Controller user's manual INDU-50 v1.95(86)EN
| 14
www.mikster.eu
No.
Default
value
Range
Description
User
settings
SF16
200°C
-99,0..999°C
Value corresponding to 20 mA for channel 3 4..20 mA input
SF17
0,0°C
-20,0..20°C
Temperature readout adjustment for channel 1
SF18
0,0°C
-20,0..20,0°C
Temperature readout adjustment for channel 2
SF19
0,0°C
-20,0..20,0°C
Temperature readout adjustment for channel 3
SF20
On
On / Off
Regulator operation in channel 1
Off always
On only in the START mode
SF21
On
On / Off
as above for channel 2
SF22
On
On / Off
as above for channel 3
SF23
-99°C
-99..400°C
Minimum allowable setpoint for channel 1
SF24
150°C
-99..400°C
Maximum allowable setpoint for channel 1
SF25
-99°C
-99..400°C
Minimum allowable setpoint for channel 2
SF26
150°C
400°C
Maximum allowable setpoint for channel 2
SF27
-
-
-
SF28
-
-
-
SF29
0
0..3
Regulator type for channel 1
0 normal hysteresis
1 reversed hysteresis
2 normal hysteresis, ’setpoint ramping” algorithm
3 PID regulator
4* relative regulator (only available for channel 3)
SF30
0
0..3
Regulator type for channel 2
SF31
0
0..4*
Regulator type for channel 3
SF32
1,0°C
0,0..5,0°C
Low hysteresis for channel 1
SF33
1,0°C
0,0..5,0°C
Low hysteresis for channel 2
SF34
1,0°C
0,0..5,0°C
Low hysteresis for channel 3
SF35
1,0°C
0,0..5,0°C
High hysteresis for channel 1
SF36
1,0°C
0,0..5,0°C
High hysteresis for channel 2
SF37
1,0°C
0,0..5,0°C
High hysteresis for channel 3
SF38
120°C
-99..999°C
Channel 3 temperature setpoint