10. Controller setup
To get into the SETUP menu, press and hold down the key and then press the key. After entering the access
code (if included in Setup cell SF 74) you can change the controller parameters.
No.
Default
value
Range
Description
User
settings
SF0
1
0..128
MODBUS network adress
SF1
0
0..4
Baud rate
0-9600, 1-19200, 2-38400, 3-57600, 4-115200
SF2
1
0..12
Channel 1 measuring input type
Standard version:
0 – PT-500
1 – PT-100
2 – PT1000
FULL CALIBRATION version (special order)
3 – 0..20mA
4 – 4..20mA
5 – thermocouple s
6 – thermocouple b
7 – thermocouple r
8 – thermocouple t
9 – thermocouple j
10 – thermocouple e
11 – thermocouple k
12 – thermocouple n
SF3
1
0..12
Measuring input type for channel 2
SF4
1
0..12
Measuring input type for channel 3
SF5
0°C
-99,0..999°C
Value corresponding to 0 mA for channel 1 0..20 mA input
SF6
200°C
-99,0..999°C
Value corresponding to 20 mA for channel 1 0..20 mA input
SF7
0°C
-99,0..999°C
Value corresponding to 0 mA for channel 2 0..20 mA input
SF8
200°C
-99,0..999°C
Value corresponding to 20 mA for channel 2 0..20 mA input
SF9
0°C
-99,0..999°C
Value corresponding to 0 mA for channel 3_0..20 mA input
SF10
200°C
-99,0..999°C
Value corresponding to 20 mA for channel 3_0..20 mA input
SF11
0°C
-99,0..999°C
Value corresponding to 4 mA for channel 1 4..20 mA input
SF12
200°C
-99,0..999°C
Value corresponding to 20 mA for channel 1 4..20 mA input
SF13
0°C
-99,0..999°C
Value corresponding to 4 mA for channel 2 4..20 mA input
SF14
200°C
-99,0..999°C
Value corresponding to 20 mA for channel 2 4..20 mA input
SF15
0°C
-99,0..999°C
Value corresponding to 4 mA for channel 3 4..20 mA input