Instructions / Assembly

24 Diamond Dual Instruction Manual
Accessory Inputs
1
SAFETY: Typically for use with photo beam device, loop
detector or other non-contact sensors
Activation of this input while the gate is closing will cause
the gate to stop and return to the opened position.
Activation of this input while the gate is opening has no
effect. (gate will continue to open)
Activation of this input while gate is idle will prevent gate
from closing.
Activation of this input while at open limit will restart the
auto close time (if enabled).
2
EXIT: Typically for use with exit loop or wand
Activation of this input will open the gate if it’s not already
at the open position.
Activation of this input while at open limit will restart the
auto close time (if enabled).
Activation of this input while gate is open will prevent gate
from closing.
3
CYCLE: Typically for use with doorbell button or hardwired
keypad
Each activation at this input will cycle the operation as
follows:
…→ OPEN → STOP → CLOSE → STOP → OPEN → …
4
EDGE SENSOR: Typically for use with contact edge
sensor
Activation of this input while gate is moving will cause it to
reverse direction for 2 seconds.
Activation of this input while idle will prevent gate from running.
5
COMMMON: Common/Negative terminal for accessory devices.
12 Volt Power (Maximum Current: 100 mA)
5
COM: Common/Negative terminal for accessory power source.
6
LOCK +: Power source for GTO/Mighty Mule accessories, i.e. Gate Opening Sensor [FM139].
Lock Outputs
6
LOCK +: Positive terminal to connect Automatic Gate Lock [FM144].
7
LOCK – : Negative terminal to connect Automatic Gate Lock.
Charge Power Inputs
8
14VAC or SOLAR: Power Input Terminals:
Input terminals for transformer or solar panel.
Non-polarity sensitive.
VAR5
VAR6
K1
PF1
K2
BATT +
BATT
K3
K4
VAR4
VAR3
VAR2
VAR1
MIN
MAX
OFF
JP1
REMOVE JUMPER FOR
PUSH TO OPEN OPTION
120
SEC.
GTO Inc. Tallahassee, FL
R4722
STALL FORCE
OPEN < JOG > CLOSE
PWR.
SET
LIMIT
1st OPR.
2nd OPR.
STATUS
AUTO CLOSE
SFTY.
EXIT
CYCLE
EDGE
SENSOR
COMMON
LOCK+
LOCK–
WHT
GRN
RED
BLK
WHT
GRN
SECOND OPR.FIRST OPR.
RED
BLK
14 VAC
OR
SOLAR
ON OFF
1
8
7
6
5
4
3
2