Product Manual

30 MM562 Installation Instructions
Input Connections
All control inputs are dry-contact, normally open, inputs. DO NOT apply external voltage sources to these
inputs.
All inputs are connected with respect to COMMON terminal.
The status LED will blink once when any input is activated.
1 COM: Circuit common (reference for all
logic input)
Two (2) terminals to provide extra
common connection point.
2 CYCLE/CLOSE: (Typically for use with
push button or hard-wired keypad)
Each activation at this input will cycle
the operation as follows:
OPEN–STOP–CLOSE–STOP–OPEN
3 SAFETY: (Typically for use with photo
beam device, loop detector or other
non-contact sensors)
Activation of this input while the gate
is closing will cause the gate to stop
and return to the opened position.
Activation of this input while the gate
is opening has no eect (gate will
continue to open).
Activation of this input while gate is
idle will prevent gate from closing.
4 EXIT/OPEN: (Typically for use with exit
loop or wand)
Activation of this input will open the
gate if it’s not already at the open
position
Activation of this input while at open
limit will restart the auto close time (if
enabled).
5 SHADOW LOOP: (Typically for use with loop detector)
This input is only monitored when the gate is at the fully open position. At any other position, activation of
this input has no eect on gate operation.
Activation of this input while gate at the fully open position will prevent gate from closing.
6 CLOSE EDGE: (Typically for use with safety edge device)
Activation of this input while the gate is closing will cause the gate to stop and reverse direction for
approximately 2 seconds.
Activation of this input while the gate is opening has no eect (gate will continue to open).
Activation of this input while gate is idle will prevent gate from closing.
7 OPEN EDGE: (Typically for use with safety edge device)
Activation of this input while the gate is opening will cause the gate to stop and reverse direction for
approximately 2 seconds.
Activation of this input while the gate is closing has no eect (gate will continue to close).
Activation of this input while gate is idle will prevent gate from opening.
1
2
3
4
7
5
6
RECEIVER
ALM
GTO RCVR.
BLK
COM
GRN
BLK
RED
CYCLE
SAFETY
EXIT
SHADOW
OPEN
EDGE
COM
CONTROL INPUTS
CLOSE
EDGE