Installation manual
SIG ALA +5VDC GND +24VDC NO NC C NO
C
5
WIRELESS DA-600 DRIVE-ALERT PAGE 2 OF 3
Under the unit cover are the address code switches (see FIGURE 1: SW1, SW2, SW3, SW4 in left lower quadrant) that must be set to
match those in the transmitter. These switches are preset at the factory for code 0000. They should only be changed if the
transmitter code is also changed. Also there is a relay time control (see FIGURE 5 TIME near middle) which is preset at minimum
of 2 seconds of alarm time. The maximum relay closer time is 12 seconds. LED 4 (VALID XMSN) is on when the Receiver detects
a valid transmission of its address and LED 3 (ALERT) is on when the relay is closed. On the outside of the Receiver is a WHISTLE
ON-OFF switch. This switch turns the whistle on or off.
DA-600 CONTROL PANEL TERMINALS:
The terminal block, TB1, provides a convenient wire connection point for external device control and test points (See FIGURE 2 for a
detailed description of the contacts available).
FIGURE 2
SIG - Received Signal Strength (e.g. 1-1.5VDC = No Signal; 1.6-2.5VDC = Signal•
+5VDC - 5 Volt DC Logic Power @ 25mA (max)•
ALA - Alarm Signal (0-1vdc = No Alarm; 4-5 VDC = Alarm)•
GND - Unit Ground•
+24VDC - Power Supply for 24VDC @ 100 mA (.1 amp) maximum accessories•
NO - Normally Open Relay Contact•
NC - Normally Closed Relay Contact•
C - Common Relay Contact•
NO - Normally Open Relay Contact•
C - Common Relay Contact•
NOTE: The DA-600 receiver will operate on 12 VDC. An auto battery with the positive (+) connected to the +24 VDC terminal and
negative (-) connected to the GND terminal will operate the DA-600. Therefore, the control panel can become portable (the sensor
is always portable) so the unit can be used in a vehicle or at a remote site.
NOTE: DO NOT PLUG THE UNIT INTO 110 VAC IF OPERATED ON BATTERY AS IT CAUSES FAILURE
The Examples below show a typical DA-600 control panel connection to an accessory
GND +24V NO NC C
External 24VDC Bell
DA-500 Whistle Switch ON
Capacitor
0.1 Microfarads 100 Volt (min)
Adding a capacitor extends the
life of the relay.
NOTE: If internal piezo whistle is not wanted, move the DA-500 Whistle Switch to
the OFF position and connect the jumper between +24 and the C Terminal
NOTE:
Limit of two external bells
BELL
RELAY
1N4004 DIODE
Adding the diode extends
the life of the relay.
External Relay Hookup
24VDC
To AC operated
CHIMES/ALARMS
GND +24V NO NC C
Connection using relay contacts switching internal power
Connection using relay contacts switching internal power
Maximum Current
Limited to 1 Ampere
Connection using dry contacts and external power
Maximum Voltage is 24V
DO NOT apply 120VAC
BELL
GND +24V NO NC C
External Power
Free Lifetime Technical Support
800-473-0213 ~ info@mierproducts.com ~ www.mierproducts.com