A power cord is required to connect the hood to the socket in the ceiling. With
extraction mode flexible ducting is also required.
Exhaust connection 6" (150mm)
Distance between cooktop and ventilation hood (S)
Provided a larger distance is not given by the manufacturer of the cooktop,
follow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INSTRUCTIONS" section.
Minimum distance S
Cooking appliance Miele
appliance
Non-Miele
appliance
Electric Cooktops 24" (610 mm)
Electric Barbeques and Fryers 26" (660 mm)
Multiburner Gas Cooktops
≤ 43,000 BTU/hr (12.6kW),
no burner > 15,000 BTU/hr (4.5 kW).
26" (660 mm) 30" (760 mm)
Multiburner Gas Cooktops
≤ 73,800 BTU/hr (21.6kW),
no burner > 16,500 BTU/hr (4.8 kW)
30" (760 mm)
Multiburner Gas Cooktops
> 73,800 BTU/hr (21.6kW),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Not possible
Single Burner Gas Cooktops
≤ 20,500 BTU/hr (6 kW)
26" (660 mm) 30" (760 mm)
Single Burner Gas Cooktops
> 20,500 BTU/hr (6 kW)
≤ 27,600 BTU/hr (8.1 kW)
30" (760 mm)
Single Burner Gas Cooktops
> 27,600 BTU/hr (8.1 kW)
Not possible