User guide
midon design
TEMP08 User Guide Version 4.0x Page 17 of 25
NW
NNW
In order for these cardinal points to line up to correct North, you must initialize the
TEMP08 first by manually (physically) setting the Wind vane to point to North and
then use the NOR command to save that direction in memory.
Wind speed is shown as an average of the speed over the previous polling
interval. The Gust speed is the maximum speed in any 1-minute period of any
polling interval. If the polling interval is set to one minute via the SPT command,
then the gust speed will not be displayed.
Rain is displayed in Inches and assumes that your rain gauge counter is
calibrated to count once for every 0.01 inch of rain. Rainfall is measured from
the time of the last reset (RST command) of the rain gauge.
General-purpose counters are used for many things. Both A and B counters of
the connected DS2423 sensor are displayed. Counts are based on the number
of counts stored in the DS2423 since the last reset (RST command) of the
counter.
The 1WIO status displays the current input status of connected DS2408ās
configured via the TYP command to be of the āIā type.
5.4. Missing Sensor Display
TEMP08 continuously polls for the presence of all sensors that have been INIād
(initialized), in other words, for sensors that are known to TEMP08. If any of the
sensors are detected as missing, the following display will result:
>MON 09:52:34
Missing Sensor #04 [9900080049199310]
When the sensor is re-connected, the display will look like this:
>MON 09:57:01
Restored Sensor #04 [9900080049199310]
Polling of sensors is done sequentially and very fast (milliseconds per sensor).
The more sensors that are equipped, however, the more time it will take for
TEMP08 to recognize a missing or re-added sensor.
It is normal to experience missing sensors from time to time due to noise on the
1-Wire bus. If any particular sensor shows very high disconnect readings, you
might want to check the wiring for that particular sensor.