Installation Guide
39 | Page
1 0-268-1 REV P7
The KID Solar Charge Controller Instructions
The AUX menu is where you set up various auxiliary input and output functions such as Auto Genstart,
Low Battery Disconnect and the Whizbang Jr. Battery status monitor.
Press the right arrow to advance to the
AUX MAIN MENU
.
Note:
Mode must be manually turned ON after changing the mode.
To turn the Mode on highlight the OFF under ON/OFF and switch it to ON. Press the Save button to
save this change. Press menu back when done. Modes will revert to OFF if the up or down arrows are
pressed before exiting.
FUNC: WBJR OFF/AUTO -
Enable/Disable/Setup the WBJR
• From the Status Menu: Press Menu Back
• Scroll to the Right and select AUX and Press Enter
• Select FUNC:WBJR
• Press the Right arrow button to Auto.
• Press the Save Button
• Press SETUP button to set the Battery Capacity.
scroll to the right to set Battery Efficiency.
Scroll right to set the Battery Temp Ref.
Scroll right to set the Battery Change %.
• Press the Save Button.
See page 44 for more information.
FUNC: Gen Start OFF/AUTO/ON -
Enable/Disable/Setup Auto Generator Staring
To use Gen Start:
• From the Status Menu: Press Menu Back
• Scroll to the Right and select AUX and Press Enter
• Select FUNC:Gen Start
• Press the Right button to Auto or *ON
• Press the Save Button
• Press SETUP button to set the battery voltage threshold to start the generator.
scroll to the right to set the Gen Start delay.
scroll to the right to set the Gen On At Volts.
Scroll right to set the Min Gen Runtime.
Scroll right to set the Max Gen Runtime.
Scroll right to set the Gen Run Confirm Voltage.
• Press the Save Button
FUNC: LBD High OFF/AUTO -
Enable/Disable/Setup Low Battery Disconnect High
• From the Status Menu: Press Menu Back
• Scroll to the Right and select AUX and Press Enter
• Select FUNC:LBD High
• Press the Right button to Auto.
• Press the Save Button
• Press SETUP button to set the AlrmON Voltage. scroll to the right to set AlrmOFF Voltage.
• Press the Save Button.
SETUP AUX FUNCTI ON
L OAD < AUX> MI SC
Important!
Do Not Exceed 12VDC
at 1 00 mA Relay Drive.
Use Normally Open (N.O.)
Contacts.