MNEDC Breaker Specifications
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
4
|
C-Series – General Specications
Electrical Tables
Table D: Lists UL Listed (489), CSA Certied (C22.2 No. 5.1-M) conguration and performance capabilities as a Molded Case
Circuit Breaker.
Table E: Lists UL Recognized, CSA Accepted congurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classied Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Table F: Lists UL Listed congurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
Notes from Table D:
1 Special catalog number required. Consult factory.
CURRENT
RATING
INTERRUPTING
CAPACITY
(AMPS)
50,000
1
Limited to 2 Poles Max from 71 - 100 Amps.
10,000 Limited to 2 Poles Max from 71 - 100 Amps.
125 DC --- 0.10 - 100 5,000 1 - 3 Poles
125 / 250 DC --- 0.10 - 50 5,000 1 or 2 Poles (2 Poles Required for 250 Volts)
0.10 - 50 10,000 1 - 3 Poles
51 - 70 5,000 1 - 3 Poles
0.10 - 50 5,000 2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
0.10 - 50
10000
1
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
240 50 / 60 1 0.10 - 30 5,000 1Pole
240 50 / 60 1 0.10 - 20 5,000 2 Pole
277 50 / 60 1 0.10 - 20 10,000 1Pole
DUAL COIL 120 50 / 60 1 0.10 - 30 10,000 ---
CIRCUIT
CONFIGURATION
FULL LOAD
AMPS
PHASE
VOLTAGE
1
0.10 - 100
50 / 60 1120 / 240
DC
CONSTRUCTION NOTES
C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS
SERIES
120
80
50 / 60
WITHOUT
BACKUP FUSE
MAX.
RATING
FREQUENCY
---