C-Series – General Specications
|
3
Electrical Tables
Table B: Lists UL Recognized and CSA Accepted congurations and performance capabilities as a Manual Motor Controller.
Table C: Lists UL Recognized, CSA Accepted , VDE and TUV Certied congurations and performance capabilities as a
Component Supplementary Protector.
Notes for Table B:
1 UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with
series fusing as stated above in note 1.
* Series, Shunt and Relay Trip - Voltage Coil Construction not current coils
Notes for Table C:
1 General Purpose ratings for UL/CSA only.
2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to
exceed 175 for 51 through 100 Amp rating.
RELAY