DIY User Manual
27 of 39
10-539-1 MN5048DIY REV -
MN5048DIY
User Manual
Parameter
no.
Parameter
name
Settings Description
24
Restart when
over
temperature
[24] DIS
Auto matic restart when over temperature is
disabled. If an over - temperature shutdown
occurs, machine will not restart to turn the output
on .
[24] ENA default
Automatic restart when over temperature is
enabled. If an over-temperature shutdown occurs,
the machine will restart when the temperature
drops.
25 Alarm enable
[25] DIS Alarm is disabled
[25] ENA default Alarm is enabled
26
Beeps while
primary source
is interrupted
[26] DIS
Alarm beep is disabled when the status of the
main input source changes
[26] ENA default
Alarm beep is enabled when the status of the
main input source changes
27
Bypass output
when over load
[27] DIS
It is disabled to automatically switch to the Mains
when the inverter is overloaded.
[27] ENA default
It is enabled to aut omatically switch to the Mains
when the inverter is overloaded.
28
Max AC charger
current
[28] 40A default Max AC charger current. S
etting range: 0~
40A;
29 Split Phase
[29] DIS default
Supply for industrial frequency transformer
(disabled )
[29] ENA
Supply for industrial frequency transformer
(enabled )
35
30
Battery
Rs485
address
setting
undervoltage
recovery point
[35]
[35]
5
1
0.4V
default
default
When the battery voltage is under voltage, the
Rs485 communication address setting range
1 ~ 254, (refer to Number [32] is valid when
set as SLA)
battery voltage needs to recover more than this
set value before the inverter starts the output
36
Max PV charger
current
[36] 40A default Max PV charger current. Setting range: 0~40A
37
Battery fully
charged
recovery point
[37] 52V default
After the battery is fully charged, it needs to be
lower than this set voltage before it can be
recharged