DIY Manual

26 | P a g e 10-543-1 REV A
DIY Manual
you want their full wattage! So, you would want to increase the wire size to #10 AWG, which can
safely carry up to 30A.
Over-Current Protection Breaker Sizing
NEC 690.9 requires that over-current protective devices (breakers, fuses) be rated to handle not
less than 125% of the maximum currents. If the over-current protective device is rated for
continuous duty (called the 3-Hr Rule), then the amp rating of the device can be at 100% or equal
to the maximum currents.
Using the same diagram we saw before, the
combined maximum current is 19.6A.
Adjusted current is 24.5A (1.25 x 19.6A)
Breaker sizing:
For non-continuous duty breaker:
1.25 x 24.5A = 30.6A
For continuous duty breaker:
1.00 x 24.5A = 24.5A
Since MidNite breakers are rated at 100%, we can use a 24.5A breaker, which does not exist. In
the above example, in real life, you would use #10 AWG for the PV homeruns connected to a 30A
breaker.
The NEC allows over-current protection to be located at one end of the PV source circuit. In the
system block diagram below, we have a combiner box, #2, with two 15A breakers serving as OCP
devices. We also have what is called the “PV Input Breaker,” #6. This could also be the OCP
device. In most installations, the combiner is located at the PV array, say a ground-mount system,
some distance away from the house. In that case, the #6 breaker acts as a simple ON/OFF switch
so that you do not have to walk out to the PV array to turn off the combiner breakers. It is
common to select the breaker for #6 slightly over-rated, so it will not nuisance trip. Continuing
with the example PV strings above, with an Isc of 9.8A x 2 strings, we know the adjusted PV amps
78V, 9.8A
78V, 9.8A
78V, 19.6A
#??? AWG
MidNite Solar breakers and fuses are rated at 100% continuous duty!