Pv V on Low
This Mode will turn Aux 1 off above a user set voltage based on the input voltage to the Classic ( V High)
and turn Aux 1 on when it hits a low voltage set point (V Low). It also allows you to set a delay time in
seconds the Classic will wait before turning Aux 1 off after reaching the V High set point. It also allows
you to set a hold time in seconds the Classic will wait before turning Aux 1 on after reaching the V Low
set point. This mode can be useful for controlling a failsafe stopping system for Hydro or Wind.
Pv V on High
This Mode will turn Aux 1 on above a user set voltage based on the input voltage to the Classic ( V High)
and turn Aux 1 off when it hits a low voltage set point (V Low). It also allows you to set a delay time in
seconds the Classic will wait before turning Aux 1 on after reaching the V High set point. It also allows
you to set a hold time in seconds the Classic will wait before turning Aux 1 off after reaching the V Low
set point. This mode can be useful for controlling a failsafe stopping system for Hydro or Wind.
Waste Not Lo
This mode will turn Aux 1 off when the Classic gets within a certain range of the voltage set points for
each charging stage (V High) and turn Aux 1 on when it gets to a low set point (V Low). These set points
are user adjustable and will allow the Absorb, Float and EQ timers to continue to run. You will adjust
these set points to negative numbers and the numbers are an offset from the voltage set point. For example
a -0.2 would turn Aux 1 off 2 tenths of a volt below your set points. This mode will allow you maximum
diversion while maintaining your 3 stage charging. It also allows you to set a delay time in seconds the
Classic will wait before turning Aux 1 off after reaching the V High set point. It also allows you to set a
hold time in seconds the Classic will wait before turning Aux 1 on after reaching the V Low set point.
Waste Not Hi
This mode will turn Aux 1 on when the Classic gets within a certain range of the voltage set points for
each charging stage (V High) and turn Aux 1 off when it gets to a low set point (V Low). These set points
are user adjustable and will allow the Absorb, Float and EQ timers to continue to run. You will adjust
these set points to negative numbers and the numbers are an offset from the voltage set point. For example
a -0.2 would turn Aux 1 on 2 tenths of a volt below your set points. This mode will allow you maximum
diversion while maintaining your 3 stage charging. It also allows you to set a delay time in seconds the
Classic will wait before turning Aux 1 on after reaching the V High set point. It also allows you to set a
hold time in seconds the Classic will wait before turning Aux 1 off after reaching the V Low set point.
Low bat disc
This mode will turn Aux 1 off when it reaches a set point based on battery voltage (V High) and turn it on
at another set point based on battery voltage (V Low). It also allows you to set a delay time in seconds the
Classic will wait before turning Aux 1 off after reaching the V High set point. It also allows you to set a
hold time in seconds the Classic will wait before turning Aux 1 on after reaching the V Low set point. This
can be used with a NC relay, when the battery gets to the set point the Classic will send 12vdc to the relay
holding it open and disconnecting the load.
Diversion