User`s manual

Page 44
1.2.3 The UPS-IPCARD Setup Utility can be installed from the CD originally provided with the
network card.
Figure 1: UPS-IPCARD Setup Utility
2) PROCEDURE
There are two separate files that required updating; these are:
mapsnmpfw_xxx.bin
mapsnmpdata_xxx.bin
where ‘xxx’ refers to the version of firmware
The ‘XXX’ version number of each file must match in order for the UPS-IPCARD to function.
The most recent firmware version can be obtained by contacting Middle Atlantic Products Technical
Support at (800) 266-7225
Create a sub-directory ‘MAP’ at the root level of the installing PC and copy the two firmware update files
to that directory (i.e. C:\MAP\).
2.1 Update mapsnmpfw_XXX.bin
Open a command prompt window
Type C: and press the ‘Enter’ key.
Type ftp xxx.xxx.xxx.xxx and press the ‘Enter’ key (where xxx.xxx.xxx.xxx is the IP Address of
the UPS-IPCARD to be updated)
When prompted enter ’user name’ and press the ‘Enter’ key (default username;admin)
When prompted enter ‘password’ and press the ‘Enter’ key (default password: admin)
Type “bin”, and press the ‘Enter’ key.
Type “put c:\map\mapsnmpfw_XXX.bin”, and press the ‘Enter’ key