RESET
Reset to Default Setting/Recover from a Forgotten Password
To reset the Middle Atlantic Network Interface Card to its default setting (including WEB login user name
and password), use the following steps.
1) Remove the two retaining screws on the card without turning off the UPS.
2) Remove the card from the expansion port.
3) Remove the jumper on the Reset pins as illustrated.(The jumper is still necessary after reset , please
do not lose or dispose of it)
4) Re-install the card into the expansion port.
5) Wait until the Green LED (RX/TX) is flashing (the frequency of the ON/OFF flashing is one second).
6) Remove the card from the expansion port.
7) Re-install the jumper on the reset pins.
8) Re-install the card into the expansion port.
9) Re-install and tighten the retaining screws.
Firmware Upgrade
1) INITIAL SETUP
1.1 Ensure that the UPS-IPCARD to be upgraded is correctly installed in the UPS, and that the UPS is
powered on.
1.2 Connect the UPS-IPCARD to the network and use “UPS-IPCARD Setup Utility” to locate and
identify the card to be upgraded. See figure 1 below:
1.2.1 Please note that the UPS-IPCARD Setup Utility will identify all UPS-IPCARDs that are on the
same subnet. Please take care to ensure that you have identified the correct card before
proceeding.
1.2.2 Please note that if the computer and the UPS-IPCARD to be upgraded are not on the same
subnet, the default gateway must be configured to correctly route between the two subnets .