05-4055A01, Rev. D GE MDS entraNET Reference Manual 23
STEP 4—CONFIGURE THE REMOTE RADIO
The instructions below summarize essential Remote settings for
tabletop testing. For detailed log-in and menu navigation instructions,
see CHAPTER 4 REMOTE RADIO MANAGEMENT, beginning on
Page 99.
Log-in and Configuration
Prepare the Remote for configuration as follows:
1. Connect a PC to the COM1 port on the radio.
2. Establish a terminal session (using HyperTerminal, for example)
using the following data parameters:
19200 bps
8 bits
no parity
one stop bit (8N1)
Table 2-1. Key AP Parameters and Defaults
Menu Item Management System Loca-
tion
Default Values or Range
IP Address Main Menu >> Network
Configuration > IP
Configuration
192.168.1.1 Contact your Network
Administrator.
If IP Address Mode (below) is set
to Dynamic, IP Address is
configured automatically.
IP Address
Mode
Main Menu >> Network
Configuration > IP
Configuration
Static Static | Dynamic
IP Netmask Main Menu >>
Network Configuration > IP
Configuration
255.255.0.0 Settable per customer
requirements
Net Address Main Menu >>
Network Configuration >
Wireless MAC Configuration
9999 1-15 alphanumeric characters*
RF Output
Power
(non-ETSI)
Main Menu >>
Radio Configuration >
900 MHz: 30 dBm
2.4 GHz: 27 dBm
900 MHz: 20–30 dBm
2.4 GHz: 17-27 dBm
RF Output
Power (ETSI)
Main Menu >>
Radio Configuration > 2.4 GHz: 20 dBm 2.4 GHz: 10-20 dBm
Password
Changes
Main Menu >>
Security Configuration >
User Passwords
Administrator Password:
admin (lower case)
Guest Password:
guest (lower case)
1–8 alphanumeric characters
Passwords are case sensitive;
can be mixed case
* We recommend setting Net Address to the last four digits of the AP serial number to reduce the chance of conflict
with other nearby entraNET systems.