Specifications

122 GE MDS entraNET Reference Manual 05-4055A01, Rev. D
5.3 IP-to-Remote Serial Application
Example
This configuration makes any data sent or received with the AP via an
IP port number appear via the serial port of a single Remote (or of all
Remotes, if “Broadcast” is selected for Remote ID).
Invisible place holder
Figure 5-2. IP-to-Remote Serial Application Diagram
Table 5-1. IP-to-Local Serial Port Application Configuration
IP-to-local serial connection (Local Serial Gateway)
Radio Location Menu Item Setting
AP (COM2) Port Status Enabled
Mode TCP
RX IP Port 30011
Baud Rate 19200
Byte Format 8N1
Buffer Size 256 Bytes
Ethernet
Terminal
or Computer
RTU
RTU
RTU
EIA-232
EIA-232
EIA-232
192.168.0.10
192.168.0.1
C
O
M
2
P
W
R
L
I
N
K
C
O
M
1
C
O
M
2
P
W
R
L
I
N
K
C
O
M
1
C
O
M
2
P
W
R
L
I
N
K
C
O
M
1
Access Point
Remotes
LAN
COM1
CO
M2
PW
R
LIN
K
Table 5-2. IP-to-Remote Serial Application Configuration
GE MDS entraNET
Radio Location
Menu Item Setting
AP (COM2) Remote ID 1155883
COM Port COM2
Mode TCP Server
Radio IP Port 30066
Remote radio (COM2) Mode COM2 in transparent data mode
Baud 19200
Format 8N1
Buffer 256
DelayChars 4