6. Disconnect the couplers without disturbing the fiber connections to the
adapters.
Method B
For Method B two launch cables are used to set the reference. The launch
cables will be canceled out for all subsequent measurements. When
measuring inplant cabling, Method B adds the loss of the 2 m launch cable,
which is considered insignificant.
1. Connect one end of a black Launch Cable to the TX (transmit) side of the
fiber adapter that is attached to OMNI
Scanner
.
2. Connect the other end of that black Launch Cable to the RX (receive)
side of the fiber adapter that is attached to OMNI
Remote
.
3. Leave the two white fiber ends dangling.
4. Connect one end of a white Launch Cable to the RX (receive) side of the
fiber adapter that is attached to OMNI
Scanner
.
5. Connect the other end of that white Launch Cable to the TX (transmit)
side of the fiber adapter that is attached to OMNI
Remote
.
6. Leave the two black fiber ends dangling.
7. Set the reference.
8. Disconnect only the following two ends: OMNI
Scanner
RX (receive) and
OMNI
Remote
RX (receive).
9. OMNI
Scanner
TX and OMNI
Remote
TX stay connected!
10. Attach the dangling fibers to the appropriate RX connectors.
RX
TX
850 nm
1300/1310 nm
RX
TX
850 nm
1300/1310 nm

2 m Launch Cables