User guide
4 - 11
OMNIScanner User Guide
Press (Pairs) to view PSNEXT graphs for other pairs.
Press ESC to exit the POWER SUM NEXT screen.
Power Sum ELFEXT
Power Sum ELFEXT is calculated from the summation of the individual
ELFEXT effects on each pair by the other three pairs.
In the POWER SUM ELFEXT screen, the worst case
margin for all pairs is shown at the top of the screen.
The pairs are displayed in the column on the left
side, followed by the PSELFEXT in decibels (dB), the
limits, and the frequency. The result for each pair is
tagged with a PASS or FAIL indicator.
Press or to toggle between the
PSELFEXT results for OMNI
Scanner
and OMNI-
Remote
.
Press (Graph) to display the PSELFEXT
graph for the currently highlighted pair. PSELFEXT is
displayed for the frequency indicated by the cursor
position.
Press (Pairs) to view PSELFEXT graphs for other pairs.
Press ESC to exit the POWER SUM ELFEXT screen.
Power Sum ACR
Power Sum ACR is calculated from the Attenuation
of the disturbing pair subtracted from the Power Sum
NEXT for the pair. The worst case Power Sum ACR
is reported for each pair.
The POWER SUM ACR screen displays the pairs in
the column on the left side, followed by the PSACR
in decibels (dB), the limits, and the frequency. The