Alarm Archives
Into Alarm Digital Channel was in its fault state for its Alarm ON Delay time and
an Alarm condition occurred.
Into High Alarm Analog Channel was in its high fault state for its Alarm ON Delay
time and an Alarm condition occurred.
Into Low Alarm Analog Channel was in its low fault state for its Alarm ON Delay time
and an Alarm condition occurred.
Into Alarm Latched Same as Into Alarm except that this time the alarm state Latched
Into High Alarm Latched Same as Into High Alarm except that this time the alarm state Latched
Into Low Alarm Latched Same as Into Low Alarm except that this time the alarm state Latched
Snooze Expired - Rearmed Channel Snooze period expired. Alarm callouts are recommencing
Alarm Cleared Channel was in a normal state for its Alarm OFF Delay time and the
Alarm condition cleared.
Acknowledgement Archives
There are 5 basic types of acknowledgements. The difference between the types of
acknowledgement tells who did the acknowledgement.
1) User Acknowledgements:
Alarm Acknowledged Channel alarm was acknowledged at this time
Alarm Acked/Unlatched Alarm Acknowledged and alarm was unlatched at this time
Alarm Reacknowledged Currently Acknowledged Channel was acknowledged again
Alarm Normal Cleared Channel Now Normal status was cleared
2) Alarm Callback acknowledgements:
Callback Acknowledged
Callback Acked/Unlatched
Callback Reacknowledged
Callback Normal Cleared
3) Alarm Acknowledgements by someone using MicroWIN 2000:
Alarm Acknowledged(mwin)
Acked/Unlatched (mwin)
Alarm Reacked (mwin)
Normal Cleared (mwin)
4) Automatic Acknowledgements by MicroWIN 2000:
Auto-Acknowledged (mwin)
Auto-Acked/Unlatch(mwin)
Auto-Reacknowledged(mwin)
Auto-Normal Cleared(mwin)
5) Dialer Callout Automatic Acknowledgement:
Callout Acknowledged
Callout Acked/Unlatched
Callout Reacknowledged
Callout Normal Cleared
Dialer Archive is unknown to this version of MicroWIN 2000
Unknown Event Used for expansion purposes in the future.
98