G.  FAULT MONITORING INTERFACE CONNECTIONS 
The MCS system is designed to accept up to four channels of dry (unpowered), 
normally open or normally closed signal lines. The system provides a small, 
pulsed sampling current to determine if the contact is open or closed. Leads 
from normally open or normally closed switches may be routed through the 
conduit port at the lower right side of the system. Connect each wire pair to its 
appropriate channel input terminal pair on the Fault Input Terminal Strip.
  Shielded, twisted pair, #20 or #22 wire (Belden 8205 or equivalent) is 
recommended. If shielded cable is used, ground the shield at the sensor and 
leave the shield floating (unconnected) at the MCS system. 
Each channel may be configured to be either normally open or normally closed. 
A channel should be normally open if the "no fault" (Green) condition is that 
condition which consists of an open circuit on that channel's wire pair. A 
channel is normally closed if the "no fault" (Green) condition is that condition 
which consists of a closed circuit on that channel's wire pair. 
The programming section of this manual will provide details on how to program 
the Mode (normally open or normally closed) of each channel as well as setting 
the Fault Delay time for each channel. 
Any unused channel should be left unconnected and programmed to a normally 
open mode. 
.