System information

MICROTEL Series 1000EX Dialer
33
z I/O Channel Type
*cc2* Report I/O channel c TYPE
**cc2nn* Program I/O channel c TYPE
**cc208Cv* Program I/O channel c to Follow Channel C’s Value
Selection of I/O channel type (cc = 01 to 41 for I/O channels starting at leftmost
slot).
N Setting Meaning
00 SPARE No Type Selected
01 Digital Input Normally Open Contact closure Normally Open
02 Digital Input Normally Closed Contact closure Normally Closed
03 Digital Output Digital Output that is user definable to
be Open or Closed
04 Analog Output (00.0 - 99.9%) Analog Output that is user definable to
be at some setting
05 Analog Input (00.0 - 99.9%) Current Percentage of an input value
06 Local Alarm Output Digital Output that Closes when there
is a local alarm
08 Follow Channel Output Digital Output that Closes depending
on the followed channel’s state
(see below)
Example- Command: **03201*
Response: Channel three type is one normally open digital input.
NOTE: When using Digital or Analog Outputs, see the section labeled Site
Control.
**cc208CCV* Program I/O channel c to Follow Channel C’s Value
Value Setting Meaning
CC
Followed Channel (01-41) The I/O Channel whose channel
status is being followed.
V
Type of Follow Channel (1-5)
0) Digital Output Follow Channel
1) Dout Follow Channel Status
2) Dout Follow Channel Alarm
3) Dout Follow Fill Algorithm
4) Dout Follow Empty Algorithm
The condition that this Output
Channel is following.
Example- Command: **04208032*
Response: Channel four type is eight digital output following channel three
alarm.