Unit installation

56 OMRCPMICRO
Status Menus
Menu
No.
Menu Line Item Line Default Values Min-Max Switch Menu No.
25 #2 Curr Alarm A.
B.
C.
D.
E.
F.
None
HicondPresStgHld
HicondPresStgDwn
FreezeProtStgDwn
LossofWaterFlow
Can't Pump Down
Freeze Stat Prot
Lo Evap pressure
Comp#4MtrProtect
Comp#3MtrProtect
Comp#2MtrProtect
Comp#1MtrProtect
Comp#4LowOil/Pwr
Comp#3LowOil/Pwr
Comp#2LowOil/Pwr
Comp#1LowOil/Pwr
Hi Cond Pressure
Mech Hi Pressure
Bad Evap PresSen
Bad Cond PresSen
BadPhase/Voltage
WaterFreezeProt
BadVoltsRatioSen
Bad Lvg WaterSen
@ ##:## -
Evap =
Cond =
SuctLine =
LiquidLn =
##/##/##
###.# psi
145 + psi
Open psi
Short psi
###.# psi
450 + psi
Open psi
Short psi
###.#°F
Open °F
Short °F
###.#°F
Open °F
Short °F
Time and date
of alarm
Conditions at
time of alarm
Menu and item
operator was viewing
just prior to alarm
26 #1 Prev Alarm A.
B.
None
HicondPresStgHld
HicondPresStrgDwn
FreezeProtStgDwn
LossofWaterFlow
Can't Pump Down
Freeze Stat Prot
Lo Evap pressure
Comp#4MtrProtect
Comp#3MtrProtect
Comp#2MtrProtect
Comp#1MtrProtect
Comp#4LowOil/Pwr
Comp#3LowOil/Pwr
Comp#2LowOil/Pwr
Comp#1LowOil/Pwr
Hi Cond Pressure
Mech Hi Pressure
Bad Evap PresSen
Bad Cond PresSen
BadPhase/Voltage
WaterFreezeProt
Bad Lvg WaterSen
@ ##:## =
##/##/## Time and date
of alarm
Table continued on next page