Unit installation

OMRCPMICRO 55
Status Menus
Menu
No.
Menu Line Item Line Default Values Min-Max Switch Menu No.
22 Alarm Spts
R-134a
A.
B.
C.
D.
E.
F.
*G.
LP CutIn =
LP CutOut =
Frz Stat =
Frze H2O =
FreezeTim =
Hi Pres =
LoSourcT =
## psi
## psi
## psi
##.# °F
### sec
### psi
##.# °F
30 psi
14 psi
26 psi
34.0°F
80 sec
266 psi
40.0°F
12-36
0-36
20-54
N/A, 0.5-40
30-120
250-425
20-75
23 Misc Setup A.
B.
C.
D.
E.
F.
G.
H.
Type =
# Compressors =
# Stages =
# Fan Stages =
Operation =
OAT Select =
# INDENT =
Remote Cond =
Air Cooled
Water Cooled
#
#
#
Chl
ChlTmp
None
Lcl
Rmt
RCP2E###
RCP2S###
Air Cooled
4
8
3
Chl
None
No
N/A
2-4
4, 6, 8
1-3
N/A
N/A
N/A
No-Yes
*Only displayed when ChlTmp operation is selected (Menu 23)
**Applicable menus for ChlTmp (Templifier) operation.
Table 9, Alarm menu
Status Menus
Menu
No.
Menu Line Item Line Default Values Min-Max Switch Menu No.
24 #1 Curr Alarm A.
B.
C.
D.
E.
F.
None
HicondPresStgHld
HicondPresStrgDwn
FreezeProtStgDwn
LossofWaterFlow
Can't Pump Down
Freeze Stat Prot
Lo Evap pressure
Comp#4MtrProtect
Comp#3MtrProtect
Comp#2MtrProtect
Comp#1MtrProtect
Comp#4LowOil/Pwr
Comp#3LowOil/Pwr
Comp#2LowOil/Pwr
Comp#1LowOil/Pwr
Hi Cond Pressure
Mech Hi Pressure
Bad Evap PresSen
Bad Cond PresSen
BadPhase/Voltage
WaterFreezeProt
BadVoltsRatioSen
Bad Lvg WaterSen
@ ##:## -
Evap =
Cond =
SuctLine =
LiquidLn =
##/##/##
###.# psi
145 + psi
Open psi
Short psi
###.# psi
450 + psi
Open psi
Short psi
###.#°F
Open °F
Short °F
###.#°F
Open °F
Short °F
Time and date
of alarm
Conditions at
time of alarm
Menu and item
operator was viewing
just prior to alarm
Table continued on next page