Unit installation
52 OMRCPMICRO
Table 8, Control menu
Status Menus
Menu
No.
Menu Line Item Line Default Values Min-Max Switch Menu No.
13 Control Mode A.
B.
Manual Unit off
Automatic
Manual Staging
AutoCirc#1-Off#2
OffCirc#1-Auto#2
Manual Stage = #
Manual Unit Off
0
N/A
0-8
1A
14 LvgWater Spts A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
Actv Spt =
Lvg Evap =
CntrlBand =
StartUpD-T =
ShutDnD-T =
MaxPullDn =
ResetOpt=
Reset Sg =
MaxChWRst =
ReturnSpt =
##.#°F
##.#°F
#.#°F
##.#°F
##.#°F
##.#°F
None
Return
4-20mA
Network
Ice
##.#mA
##.#°F
##.#°F
44.0°F
3.0°F
3.0°F
1.5°F
0.5°F/min
None
10.0ºF
54.0°F
10-80
1.0-5.0
0.0-5.0
0.0-3.0
0.1-1.0
0-45
15-80
4A
4A
14** LvgWater Spts A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
Actv Spt =
Lvg Evap =
LvgCond =
CntrlBand =
StartUpD-T =
ShutDnD-T =
MaxPullDn =
ResetOpt=
Reset Sg =
MaxChWRst =
###.#°F
##.#°F
###°F
#.#°F
##.#°F
##.#°F
##.#°F
none
4-20mA
Network
##.#mA
##.#°F
44.0°F
115°F
3.0°F
3.0°F
1.5°F
0.5°F
None
10.0ºF
10-80
85-220
1.0-5.0
0.0-5.0
0.0-3.0
0.1-1.0
0-45
4A
4A
4D
15 SoftLoad Spts A.
B.
C.
D.
Time Left =
SoftLoad =
SoftLdMaxStg =
LoadDelay =
### min
### min
#
### sec
20 min
4
15 sec
0-254
0-254
1-8
0-254
16 CompressorSpt A.
B.
C.
D.
Lead Circuit
InterStg =
MinSt-St =
Min SP-St =
Auto
#1
#2
### sec
### min
### min
Auto
180 sec
15 min
5 min
N/A
60-240
5-40
3-30
17 Head Pres Spt A.
B.
C.
D.
E.
MinLift-35% =
MinLift-100%
DeadBandMult =
StageUpErr =
StageDnErr =
###
###
#.#
###
###
85 psi
140 psi
1.0
400 p/s
100 p/s
60-140
120-180
0.8-1.3
300-990
50-400
18 Demand Limits A. Demand Lim =
Demand Sg =
# stg
###.#mA
0-8
0-20mA
18** Chiller/Templ Chl/Tmp Sig = Temp
Chil
19 Time/Date A.
B.
Time
B. Sun
##:
:##:
##
/ /
##/ /
/##/
/ /##
Current hour
Current min
Current sec
Current day
Current month
Current date
Current year
0-23
0-59
0-59
N/A
1-12
1-31
0-99
20 Schedule A.
B.
Override =
NMP Schedule=
##.## Hr
##
N/A
00.0
N/A
0-63.50
1-32
C. Sun
Sun
Sun
Sun
##: - :
:##- :
: -##:
: - :##
0
0
23
59
0-23
0-59
0-23
0-59
D. Mon
Mon
Mon
Mon
##: - :
:##- :
: -##:
: - :##
0
0
23
59
0-23
0-59
0-23
0-59