Specifications

130BB572.10
2800
607
IP/21
NEMA 1
IP/54
NEMA 12
4200
m3/Hr
2472
CFM
1854
CFM
3150
m3/Hr
2900
CFM
4925
m3/Hr
2280
2205
1497
Illustration 5.26 Mechanical Dimensions (mm), F13
12-Pulse Mechanical Dimension Tables
Frame size F8 F9 F10 F11 F12 F13
High overload rated
power - 160%
overload torque
250-400 kW
(380-500 V)
355-560 kW
(525-690 V)
250-400 kW
(380-500 V)
355-560 kW
(525-690 V)
450-630 kW
(380-500 V)
630-800 kW
(525-690 V)
450-630 kW
(380-500 V)
630-800 kW
(525-690 V)
710-800 kW
(380-500 V)
900-1200 kW
(525-690 V)
710-800 kW
(380-500 V)
900-1200 kW
(525-690 V)
IP
NEMA
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
Shipping
dimensions
[mm]
Height 2324
Width 970 1568 1760 2559 2160 2960
Depth 1130
Drive
dimensions
[mm]
Height 2204
Width 800 1400 1600 2200 2000 2600
Depth 606
Max weight [kg] 447 669 893 1116 1037 1259
Table 5.22 Mechanical Dimensions, 12-Pulse Units, Frame Sizes F8-F13
How to Install VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 95
5
5