4.2.5 Ordering Numbers: Brake Resistors
For brake resistor selection information, refer to the Brake Resistor Design Guide
Use this table to determine the minimum resistance applicable to each frequency converter size.
380-480 V AC
Drive data
Aqua FC202 [T4] Pm (NO) [kW]
Number of brake choppers
1)
R
min
N110 110 1 3.6
N132 132 1 3
N160 160 1 2.5
N200 200 1 2
N250 250 1 1.6
N315 315 1 1.2
P355 355 1 1.2
P400 400 1 1.2
P500 500 2 0.9
P560 560 2 0.9
P630 630 2 0.8
P710 710 2 0.7
P800 800 3 0.6
P1M0 1000 3 0.5
Table 4.21 Brake Chopper Data, 380-480 V
525-690 V AC
Drive data
Aqua FC202 [T7] Pm (NO) [kW]
Number of brake choppers
1)
R
min
N75K 75 1 13.5
N90K 90 1 8.8
N110 110 1 8.2
N132 132 1 6.6
N160 160 1 4.2
N200 200 1 4.2
N250 250 1 3.4
N315 315 1 2.3
N400 400 1 2.3
P450 450 1 2.3
P500 500 1 2.1
P560 560 1 2
P630 630 1 2
P710 710 2 1.3
P800 800 2 1.1
P900 900 2 1.1
P1M0 1000 3 1
P1M2 1200 3 0.8
P1M4 1400 3 0.7
Table 4.22 Brake Chopper Data 525-690 V
R
min
=Minimum brake resistance that can be used with this frequency converter . If the frequency converter includes multiple brake choppers, the
resistance value is the sum of all resisters in parallel
R
br, nom
=Nominal resistance required to achieve 150% braking torque.
1)
Larger frequency converters include multiple inverter modules with a brake chopper in each inverter. Connect equal resistors to each brake
chopper.
How to Order VLT® HVAC Drive FC 102 Design Guide
76 MG16C102 - Rev. 2013-08-20