Specifications
Code
number
AHF005
IP00
IP20
Code
number
AHF010
IP00
IP20
Filter
current
rating
Typical
motor
VLT model and
current ratings
Losses
Acoustic
noise
Frame size
AHF005 AHF010
[A] [HP] [HP] [A] [W] [W] [dBA] AHF005 AHF010
130B1799
130B1764
130B1782
130B1496
183 150 N110 183 1080 743 <75 X6 X6
130B1900
130B1765
130B1783
130B1497
231 200 N132 231 1194 864 <75 X7 X7
130B2200
130B1766
130B1784
130B1498
291 250 N160 291 1288 905 <75 X8 X7
130B2257
130B1768
130B1785
130B1499
355 300 N200 348 1406 952 <75 X8 X7
130B3168
130B3167
130B3166
130B3165
380 Used for paralleling at 355 kW 1510 1175 <77 X8 X7
130B2259
130B1769
130B1786
130B1751
436 350 N250 436 1852 1542 <77 X8 X8
130B1900+
130B2200
130B1765+
130B1766
130B1783+
130B1784
130B1497+
130B1498
522 450 N315 531 2482 1769 <80
Table 4.12 Advanced Harmonic Filters 440-480 V, 60 Hz, D-frame
Code number AHF005
IP00/IP20
Code number AHF010
IP00/IP20
Filter
current
rating
Typical
motor
VLT model/
current
ratings
Losses
Acoustic
noise
Frame size
AHF005 AHF010
[A] [HP] [kW] [A] [W] [W] [dBA] AHF005
AHF01
0
2x130B2200
2x130B1766
2x130B1784
2x130B1498
582 500 P355 580 2576 1810 <80
130B2200+130B3166
130B1766+130B3167
130B1784+130B3166
130B1498+130B3165
671 550 P400 667 2798 2080 <80
2x130B2257
2x130B1768
2x130B1785
2x130B1499
710 600 P450 711 2812 1904 <80
2x130B3168
2x130B3167
2x130B3166
2x130B3165
760 650 P500 759 3020 2350 <80
2x130B2259
2x130B1769
2x130B1786
2x130B1751
872 750 P560 867 3704 3084 <80
3x130B2257
3x130B1768
3x130B1785
3x130B1499
1065 900 P630 1022 4218 2856 <80
3x130B3168
3x130B3167
3x130B3166
3x130B3165
1140 1000 P710 1129 4530 3525 <80
3x130B2259
3x130B1769
3x130B1786
3x130B1751
1308 1200 P800 1344 5556 4626 <80
2x130B2257+2x130B2259
2x130B1768+2x130B1768
2x130B1785 +2x130B1786
2x130B1499+2x130B1751
1582 1350 P1M0 1490 6516 5988 <80
Table 4.13 Advanced Harmonic Filters, 440-480 V, 60 Hz, E- and F-frames
How to Order VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 69