Specifications

Code
number
AHF005
IP00
IP20
Code
number
AHF010
IP00
IP20
Filter
current
rating
Typical
motor
VLT model and
current ratings
Losses
Acoustic
noise
Frame size
AHF005 AHF010
[A] [kW] [kW] [A] [W] [W] [dBA] AHF005 AHF010
130B3131
130B2869
130B3090
130B2500
204 110 N110 204 1080 743 <75 X6 X6
130B3132
130B2870
130B3091
130B2700
251 132 N132 251 1194 864 <75 X7 X7
130B3133
130B2871
130B3092
130B2819
304 160 N160 304 1288 905 <75 X8 X7
130B3157
130B3156
130B3155
130B3154
325
Paralleling for 355 kW
1406 952 <75 X8 X7
130B3134
130B2872
130B3093
130B2855
381 200 N200 381 1510 1175 <77 X8 X7
130B3135
130B2873
130B3094
130B2856
480 250 N250 472 1850 1542 <77 X8 X8
2x130B3133
2x130B2871
2x130B3092
2x130B2819
608 315 N315 590 2576 1810 <80
Table 4.10 Advanced Harmonic Filters, 380-415 V, 60 Hz, D-frame
Code
number AHF005
IP00
IP20
Code
number AHF010
IP00
IP20
Filter
current
rating
Typical
motor
VLT model/
current
ratings
Losses
Acoustic
noise
Frame size
AHF005 AHF010
[A] [kW] [kW] [A] [W] [W] [dBA]
AHF00
5
AHF010
2x130B3157
2x130B3156
2x130B3155
2x130B3154
650 315 P355 647 2812 1904 <80
130B3133+130B3134
130B2871+130B2872
130B3092+130B3093
130B2819+130B2855
685 355 P400 684 2798 2080 <80
2x130B3134
2x130B2872
2x130B3093
2x130B2855
762 400 P450 779 3020 2350 <80
130B3134+130B3135
130B2872+130B3135
130B3093+130B3094
130B2855+130B2856
861 450 P500 857 3362 2717 <80
2x130B3135
2x130B2873
2x130B3094
2x130B2856
960 500 P560 964 3704 3084 <80
3x130B3134
3x130B2872
3x130B3093
3x130B2855
1140 560 P630 1090 4530 3525 <80
2x130B3134+130B3135
2x130B2872+130B2873
2x130B3093+130B3094
2x130B2855+130B2856
1240 630 P710 1227 4872 3892 <80
3x130B3135
3x130B2873
3x130B3094
3x130B2856
1440 710 P800 1422 5556 4626 <80
2x130B3134+2x130B3135
2x130B2872+2x130B2873
2x130B3093+2x130B3094
2x130B2855+2x130B2856
1722 800 P1M0 1675 6724 5434 <80
Table 4.11 Advanced Harmonic Filters, 380-415 V, 60 Hz, E- and F-frames
How to Order VLT® HVAC Drive FC 102 Design Guide
68 MG16C102 - Rev. 2013-08-20
4
4