Specifications

4.2.2 Advanced Harmonic Filters
Harmonic filters are used to reduce mains harmonics:
AHF 010: 10% current distortion
AHF 005: 5% current distortion
For detailed information on advanced harmonic filters, see the Advanced Harmonic Filters Design Guide.
Code
number
AHF005
IP00
IP20
Code
number
AHF010
IP00
IP20
Filter
current
rating
Typical
motor
VLT model and
current ratings
Losses
Acoustic
noise
Frame size
AHF005 AHF010
[A] [kW] [kW] [A] [W] [W] [dBA] AHF005 AHF010
130B1446
130B1251
130B1295
130B1214
204 110 N110 204 1080 742 <75 X6 X6
130B1447
130B1258
130B1369
130B1215
251 132 N132 251 1195 864 <75 X7 X7
130B1448
130B1259
130B1370
130B1216
304 160 N160 304 1288 905 <75 X7 X7
130B3153
130B3152
130B3151
130B3136
325
Paralleling for 355 kW
1406 952 <75 X8 X7
130B1449
130B1260
130B1389
130B1217
381 200 N200 381 1510 1175 <77 X8 X7
130B1469
130B1261
130B1391
130B1228
480 250 N250 472 1852 1542 <77 X8 X8
2x130B1448
2x130B1259
2x130B1370
2x130B1216
608 315 N315 590 2576 1810 <80
Table 4.8 Advanced Harmonic Filters 380-415 V, 50 Hz, D-frame
Code number
AHF005
IP00
IP20
Code number
AHF010
IP00
IP20
Filter
current
rating
Typical
motor
VLT model
and current
ratings
Losses
Acoustic
noise
Frame size
AHF005 AHF010
[A] [kW] [kW] [A] [W] [W] [dBA] AHF005 AHF010
2x130B3153
2x130B3152
2x130B3151
2x130B3136
650 355 P355 647 2812 1904 <80
130B1448+130B1449
130B1259+130B1260
130B1370+130B1389
130B1216+130B1217
685 400 P400 684 2798 2080 <80
2x130B1449
2x130B1260
2x130B1389
2x130B1217
762 450 P450 779 3020 2350 <80
130B1449+130B1469
130B1260+130B1261
130B1389+130B1391
130B1217+130B1228
861 500 P500 857 3362 2717 <80
2x130B1469
2x130B1261
2x130B1391
2x130B1228
960 560 P560 964 3704 3084 <80
3x130B1449
3x130B1260
3x130B1389
3x130B1217
1140 630 P630 1090 4530 3525 <80
2x130B1449+130B1469
2x130B1260+130B1261
2x130B1389+130B1391
2x130B1217+130B1228
1240 710 P710 1227 4872 3892 <80
3x130B1469
3x1301261
3x130B1391
3x130B1228
1440 800 P800 1422 5556 4626 <80
2x130B1449+2x130B1469
2x130B1260+2x130B1261
2x130B1389+2x130B1391
2x130B1217+2x130B1228
1720 1000 P1000 1675 6724 5434 <80
Table 4.9 Advanced Harmonic Filters 380-415 V, 50 Hz, E- and F-frames
How to Order VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 67
4
4