Specifications
3.1.11.7 Heat Sink Access Panel
An optional heat sink access panel is available to facilitate
cleaning of the heat sink. Debris buildup is typical in
environments prone to airborne contaminants, such as the
textile industry.
3.1.11.8 Mains Disconnect
The disconnect option is available in both varieties of
option cabinets. The position of the disconnect changes
based on the size of the options cabinet and whether
other options are present. Table 3.10 provides more detail
about which disconnects are used.
Voltage Frequency converter
model
Disconnect manufacturer
and type
380–500 V N110T5–N160T4 ABB OT400U03
N200T5–N315T4 ABB OT600U03
525–690 V N75KT7–N160T7 ABB OT400U03
N200T7–N400T7 ABB OT600U03
Table 3.10 Mains Disconnect Information
3.1.11.9 Contactor
A customer-supplied 230 V AC 50/60 Hz signal powers the
contactor.
Voltage Frequency
converter
model
Contactor
manufacturer and
type
IEC
utilisation
category
380–500 V N110T5–N160T4 GE CK95BE311N AC-3
N200T5–N250T4 GE CK11CE311N AC-3
N315T4 GE CK11CE311N AC-1
525–690 V N75KT7–N160T7 GE CK95BE311N AC-3
N200T7–N400T7 GE CK11CE311N AC-3
Table 3.11 Contactor Information
NOTICE
In applications requiring UL listing, when the frequency
converter is supplied with a contactor, the customer
must provide external fusing to maintain the UL rating
of the frequency converter and a short circuit current
rating of 100,000 A. See 5.2.9 Fuses 5.2.10 Fuse Specifi-
cations for fuse recommendations.
3.1.11.10 Circuit Breaker
Table 3.12 provides details on the type of circuit breaker
provided as an option with the various units and power
ranges.
[V] Frequency converter
model
Circuit breaker manufacturer
and type
380–500 N110T5–N132T5 ABB T5L400TW
N160T5 ABB T5LQ400TW
N200T5 ABB T6L600TW
N250T5 ABB T6LQ600TW
N315T5 ABB T6LQ800TW
525–690 N75KT7–N160T7 ABB T5L400TW
N200T7–N315T7 ABB T6L600TW
N400T7 ABB T6LQ600TW
Table 3.12 Circuit Breaker Information
3.1.12 F-frame Panel Options
Space Heaters and Thermostat
There are space heaters mounted on the cabinet interior of
F-frame frequency converters. These heaters are controlled
by an automatic thermostat and help control humidity
inside the enclosure. The thermostat default settings turn
on the heaters at 10 °C (50 °F) and turn them off at 15.6
°C (60 °F).
Cabinet Light with Power Outlet
A light mounted on the cabinet interior of F-frame
frequency converters increases visibility during servicing
and maintenance. The housing includes a power outlet for
temporarily powering tools or other devices, available in 2
voltages:
•
230 V, 50 Hz, 2.5 A, CE/ENEC
•
120 V, 60 Hz, 5 A, UL/cUL
Transformer Tap Set-up
If the cabinet light & outlet and/or the space heaters &
thermostat are installed, transformer T1 requires its taps to
be set to the proper input voltage. A 380-480/500 V drive
will initially be set to the 525 V tap and a 525-690 V drive
will be set to the 690 V tap to ensure no over-voltage of
secondary equipment occurs if the tap is not changed
before applying power. See Table 3.13 to set the proper
tap at terminal T1 located in the rectifier cabinet.
Input voltage range Tap to select
380 V-440 V 400 V
441 V-490 V 460 V
491 V-550 V 525 V
551 V-625 V 575 V
626 V-660 V 660 V
661 V-690 V 690 V
Table 3.13 Transformer Tap Setup
NAMUR Terminals
NAMUR is an international association of automation
technology users in the process industries, primarily
chemical and pharmaceutical industries in Germany.
Selecting this option provides terminals organized and
labeled to the specifications of the NAMUR standard for
Selection VLT® HVAC Drive FC 102 Design Guide