Specifications

3.1.3 Analog Voltage Inputs - Terminal X30/10-12
Parameters for set-up: 6-3*, 6-4* and 16-76
Number of analog voltage inputs Standardized input signal Tolerance Resolution Max. Input impedance
2 0-10 V DC ± 20 V continuously 10 bits
Approx. 5 KΩ
Table 3.2 Analog Voltage Inputs - Terminal X30/10-12
3.1.4 Digital Outputs - Terminal X30/5-7
Parameters for set-up: 5-32 and 5-33
Number of digital outputs Output level Tolerance Max. Impedance
2 0 or 2 V DC ± 4 V
600 Ω
Table 3.3 Digital Outputs - Terminal X30/5-7
3.1.5 Analog Outputs - Terminal X30/5+8
Parameters for set-up: 6-6* and 16-77
Number of analog outputs Output signal level Tolerance Max. Impedance
1 0/4 - 20 mA ± 0.1 mA
< 500 Ω
Table 3.4 Analog Outputs - Terminal X30/5+8
3.1.6 Relay Option MCB 105
The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data:
Max terminal load (AC-1)
1)
(Resistive load) 240 V AC 2A
Max terminal load (AC-15 )
1)
(Inductive load @ cosφ 0.4) 240 V AC 0.2 A
Max terminal load (DC-1)
1)
(Resistive load) 24 V DC 1 A
Max terminal load (DC-13)
1)
(Inductive load) 24 V DC 0.1 A
Min terminal load (DC) 5 V 10 mA
Max switching rate at rated load/min load 6 min
-1
/20 s
-1
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately, it includes:
Relay module MCB 105
Extended LCP frame and enlarged terminal cover
Label for covering access to switches S201, S202 and S801
Cable strips for fastening cables to relay module
Adding the MCB 105 option:
1. Disconnect the power to the live part connections on relay terminals.
2. Do not mix live parts with control signals (PELV).
3.
Select the relay functions in E-24 Function Relay [6-8], E-26 On Delay, Relay [6-8] and E-27 Off Delay, Relay [6-8].
NOTICE
(Index [6] is relay 7, index [7] is relay 8, and index [8] is relay 9)
Selection VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 51