Specifications
3.1.3 Analog Voltage Inputs - Terminal X30/10-12
Parameters for set-up: 6-3*, 6-4* and 16-76
Number of analog voltage inputs Standardized input signal Tolerance Resolution Max. Input impedance
2 0-10 V DC ± 20 V continuously 10 bits
Approx. 5 KΩ
Table 3.2 Analog Voltage Inputs - Terminal X30/10-12
3.1.4 Digital Outputs - Terminal X30/5-7
Parameters for set-up: 5-32 and 5-33
Number of digital outputs Output level Tolerance Max. Impedance
2 0 or 2 V DC ± 4 V
≥ 600 Ω
Table 3.3 Digital Outputs - Terminal X30/5-7
3.1.5 Analog Outputs - Terminal X30/5+8
Parameters for set-up: 6-6* and 16-77
Number of analog outputs Output signal level Tolerance Max. Impedance
1 0/4 - 20 mA ± 0.1 mA
< 500 Ω
Table 3.4 Analog Outputs - Terminal X30/5+8
3.1.6 Relay Option MCB 105
The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data:
Max terminal load (AC-1)
1)
(Resistive load) 240 V AC 2A
Max terminal load (AC-15 )
1)
(Inductive load @ cosφ 0.4) 240 V AC 0.2 A
Max terminal load (DC-1)
1)
(Resistive load) 24 V DC 1 A
Max terminal load (DC-13)
1)
(Inductive load) 24 V DC 0.1 A
Min terminal load (DC) 5 V 10 mA
Max switching rate at rated load/min load 6 min
-1
/20 s
-1
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately, it includes:
•
Relay module MCB 105
•
Extended LCP frame and enlarged terminal cover
•
Label for covering access to switches S201, S202 and S801
•
Cable strips for fastening cables to relay module
Adding the MCB 105 option:
1. Disconnect the power to the live part connections on relay terminals.
2. Do not mix live parts with control signals (PELV).
3.
Select the relay functions in E-24 Function Relay [6-8], E-26 On Delay, Relay [6-8] and E-27 Off Delay, Relay [6-8].
NOTICE
(Index [6] is relay 7, index [7] is relay 8, and index [8] is relay 9)
Selection VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 51
3