Specifications

3 Selection
3.1 Options and Accessories
Danfoss offers a wide range of options and accessories.
3.1.1 General Purpose Input Output
Module MCB 101
MCB 101 is used for extending the number of digital and
analogue inputs and outputs.
MCB 101 must be fitted into slot B in the frequency
converter.
MCB 101 option module
Extended LCP frame
Terminal cover
General Purpose I/O
SW. ver. XX.XX
MCB 101
FC Series
Code No. 130BXXXX
B slot
X30/
AIN4
78654321 9 10 11 12
AIN3
GND(2)
24V
AOUT2
DOUT4
DOUT3
GND(1)
DIN7
COM
DIN
DIN8
DIN9
130BA208.10
Illustration 3.1 MCB 101
Galvanic isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other
inputs/outputs on the MCB 101 and in the control card of
the frequency converter. Digital/analog outputs in the MCB
101 are galvanically isolated from other inputs/outputs on
the MCB 101, but not from those on the control card.
If the digital inputs 7, 8 or 9 are to be switched using the
internal 24 V power supply (terminal 9), the connection
between terminals 1 and 5, which is shown in
Illustration 3.2 has to be established.
130BA209.10
1
23
45
6
7
8
9 10
11
12
COM DIN
DIN7
DIN8
DIN9
GND(1)
DOUT3
0/24VDC
DOUT4
0/24VDC
AOUT2
0/4-20mA
24V
GND(2)
AIN3
AIN4
RIN=
5kohm
RIN=
10kohm
0-10
VDC
0-10
VDC
0V 24V
0V 24V
24V DC0V
0V24V DC
<500 ohm
>600 ohm
>600 ohm
X30/
DIG IN
DIG &
ANALOG
OUT
ANALOG
IN
CPU
CAN BUS
CPU
Control card (FC 100/200/300)
General Purpose
I/O option MCB 101
PLC
(PNP)
PLC
(NPN)
Illustration 3.2 Principle Diagram
3.1.2 Digital Inputs - Terminal X30/1-4
Parameters for set-up: 5-16, 5-17 and 5-18
Number of
digital inputs
Voltage level Voltage levels Tolerance Max. Input impedance
3 0-24 V DC PNP type:
Common = 0 V
Logic “0”: Input < 5 V DC
Logic “0”: Input > 10 V DC
NPN type:
Common = 24 V
Logic “0”: Input > 19 V DC
Logic “0”: Input < 14 V DC
± 28 V continuous
± 37 V in minimum 10
sec.
Approx. 5
Table 3.1 Digital Inputs - Terminal X30/1-4
Selection VLT® HVAC Drive FC 102 Design Guide
50 MG16C102 - Rev. 2013-08-20
3
3