Specifications

2.8.11 Tuning the Closed Loop Controller
Once the closed loop controller has been set up, the
performance of the controller should be tested. In many
cases, its performance may be acceptable using the default
values of CL-93 PID Proportional Gain and CL-94 PID Integral
Time. However, in some cases it may be helpful to
optimize these parameter values to provide faster system
response while still controlling speed overshoot.
2.8.12 Manual PID Adjustment
1. Start the motor.
2.
Set CL-93 PID Proportional Gain to 0.3 and
increase it until the feedback signal begins to
oscillate. If necessary, start and stop the
frequency converter or make step changes in the
set-point reference to attempt to cause
oscillation.
3. Reduce the PID proportional gain until the
feedback signal stabilizes. Reduce the propor-
tional gain by 40-60%.
4.
Set CL-94 PID Integral Time to 20 sec. and reduce
it until the feedback signal begins to oscillate. If
necessary, start and stop the frequency converter
or make step changes in the set-point reference
to attempt to cause oscillation.
5. Increase the PID integral time until the feedback
signal stabilizes. Increase of the integral time by
15-50%.
6.
CL-95 PID Differentiation Time should only be used
for fast-acting systems. The typical value is 25%
of CL-94 PID Integral Time. The differential
function should only be used when the setting of
the proportional gain and the integral time has
been fully optimized. Make sure that oscillations
of the feedback signal are sufficiently dampened
by the low-pass filter for the feedback signal
(parameters 6-16, 6-26, 5-54 or 5-59 as required).
Introduction VLT® HVAC Drive FC 102 Design Guide
38 MG16C102 - Rev. 2013-08-20
2
2