Specifications
2.8.10 Programming Order
NOTICE
This example assumes an induction motor is used, so P-20 Motor Construction = [0] Asynchron.
Function Parameter no. Setting
1) Make sure the motor runs properly. Do the following:
Set the motor parameters using nameplate data. 1-2* As specified by motor name plate
Run Automatic Motor Adaptation (AMA). 1-29
[1] Enable complete AMAand then run the AMA
function.
2) Check that the motor is running in the right direction.
Run motor rotation check. 1-28 If the motor runs in the wrong direction, remove
power temporarily and reverse two of the motor
phases.
3) Make sure the frequency converter limits are set to safe values
Check that the ramp settings are within capabilities of
the frequency converter and allowed application
operating specifications.
3-41
3-42
60 s
60 s
Depends on motor/load size!
Also active in Hand mode.
Prohibit the motor from reversing (if necessary) 4-10
[0] Clockwise
Set acceptable limits for the motor speed. 4-12
4-14
4-19
10 Hz, Motor min speed
50 Hz, Motor max speed
50 Hz, Drive max output frequency
Switch from open loop to closed loop. 1-00
[3] Closed Loop
4) Configure the feedback to the PID controller.
Select the appropriate reference/feedback unit. 20-12
[71] Bar
5) Configure the set-point reference for the PID controller.
Set acceptable limits for the set-point reference. 20-13
20-14
0 Bar
10 Bar
Choose current or voltage by switches S201 / S202
6) Scale the analogue inputs used for set-point reference and feedback.
Scale analogue Input 53 for the pressure range of the
potentiometer (0–10 Bar, 0–10 V).
6-10
6-11
6-14
6-15
0 V
10 V (default)
0 Bar
10 Bar
Scale analogue input 54 for pressure sensor (0–10 Bar,
4–20 mA)
6-22
6-23
6-24
6-25
4 mA
20 mA (default)
0 Bar
10 Bar
7) Tune the PID controller parameters.
Adjust the closed loop controller, if needed. 20-93
20-94
See Optimization of the PID Controller, below.
8) Finished
Save the parameter setting to the LCP 0-50
[1] All to LCP
Table 2.9 Programming Order