Specifications

2.7.19 Condenser Pumps
Condenser water pumps are primarily used to circulate
water through the condenser section of water-cooled
chillers and their associated cooling tower. The condenser
water absorbs the heat from the condenser section and
releases it into the atmosphere in the cooling tower. These
systems provide the most efficient means of creating
chilled water. They are as much as 20% more efficient than
air cooled chillers.
2.7.20 The VLT Solution
Frequency converters can be added to condenser water
pumps instead of balancing the pumps with a throttling
valve or trimming the pump impeller.
Using a frequency converter instead of a throttling valve
saves the energy that the valve would otherwise have
absorbed. This change can amount to savings of 15–20%
or more. Trimming the pump impeller is irreversible, so if
the conditions change and higher flow is required the
impeller must be replaced.
Frequency
converter
Water
Inlet
Water
Outlet
BASIN
Flow or pressure sensor
Condenser
Water pump
Throttling
valve
Supply
CHILLER
130BB452.10
Illustration 2.14 Frequency Converter used with a Condenser Pump
Introduction VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 27
2
2