Specifications
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load) 80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load) 24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load) 240V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load) 50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load) 24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2A
Control card, 10 V DC output
Terminal number 50
Output voltage 10.5 V ± 0.5 V
Max. load 25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0-590 Hz ± 0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33) ≤ 2 ms
Speed control range (open loop) 1:100 of synchronous speed
Speed accuracy (open loop) 30–4000 rpm: Maximum error of ±8 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings
Enclosure type D1h/D2h/E1/E2 IP00/chassis
Enclosure type D3h/D4h IP20/chassis
Enclosure type D1h/D2h, E1, F1-F4, F8-F13 IP21/Type 1, IP54/Type 12
Vibration test enclosure D/E/F 1 g
Maximum relative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode) Max. 45 °C
Maximum ambient temperature with reduced load 55 °C
Derating for high ambient temperature, see 8.5.2 Derating for Ambient Temperature
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 - +65/70 °C
Maximum altitude above sea level without derating 1000 m
Maximum altitude above sea level with derating 3000 m
Derating for high altitude, see 8.5 Special Conditions
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See 8.5 Special Conditions for more information.
Control card performance
Scan interval 5 ms
Control card, USB serial communication
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
General Specifications and ... VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 193
8