Specifications

Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips when the temperature reaches
95 °C ± 5 °C. An overload temperature cannot be reset until the temperature of the heatsink is below 70 °C ± 5 °C
(Guideline - these temperatures vary for different power sizes and enclosures). The frequency converter has an
auto derating function to prevent its heatsink reaching 95 °C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply
Supply terminals (6-pulse) L1, L2, L3
Supply terminals (12-pulse) L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
Supply voltage 380-480 V ±10%
Supply voltage 525-600 V ±10%
Supply voltage 525-690 V ±10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage. Power-up and full
torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage.
Supply frequency 50/60 Hz +4/-6%
The frequency converter power supply is tested in accordance with IEC61000-4-28, 50 Hz +4/-6%.
Max. imbalance temporary between mains phases 3.0% of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement power factor (cosφ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) enclosure type D, E, F maximum 1 time/2 min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage 0–100 % of supply voltage
Output frequency 0-590 Hz
Switching on output Unlimited
Ramp times 1–3600 s
Torque characteristics
Starting torque (constant torque) maximum 110% for 1 minute
*
Starting torque maximum 135% up to 0.5 s
*
Overload torque (constant torque) maximum 110% for 1 minute
*
*Percentage relates to nominal torque.