Specifications
Mains Supply 525-690 V AC
P450 P500 P560 P630 P710 P800 P900 P1M0 P1M2 P1M4
Normal overload 110% for 1 Minute
NO NO NO NO NO NO NO NO NO NO
Typical Shaft Output [HP] at 525-550 V 355 400 450 500 560 670 750 850 1000 1100
Typical Shaft Output [kW] at 690 450 500 560 630 710 800 900 1000 1200 1400
Typical Shaft Output [HP] at 575 450 500 600 650 750 950 1050 1150 1350 1550
IP 21/ NEMA 1 at 525 V F8/F9 F10/F11 F12/F13
IP 21/ NEMA 1 at 575 V F8/F9 F10/F11 F12/F13
IP 21/ NEMA 1 at 690 V F8/F9 F10/F11 F12/F13
Output Current
Continuous (6 x 525-550 V) [A] 470 523 596 630 763 889 988 1108 1317 1479
Intermittent (6 x 550 V) 515 575 656 693 839 978 1087 1219 1449 1627
Continuous (6 x 551-690 V) [A] 450 500 570 630 730 850 945 1060 1260 1415
Intermittent (6 x 551-690 V) [A] 495 550 627 693 803 935 1040 1166 1386 1557
Continuous KVA (550 V) [KVA] 448 498 568 600 727 847 941 1056 1255 1409
Continuous KVA (575 V) [KVA] 448 498 568 627 727 847 941 1056 1255 1409
Continuous KVA (690 V) [KVA] 538 598 681 753 872 1016 1129 1267 1506 1691
Max Input Current
Continuous (6 x 550 V) [A] 453 504 574 607 743 866 962 1079 1282 1440
Continuous (6 x 575 V) [A] 434 482 549 607 711 828 920 1032 1227 1378
Continuous (6 x 690 V) [A] 434 482 549 607 711 828 920 1032 1227 1378
Max. external mains fuses
1)
630 630 630 630 900 900 900 1600 2000 2500
Max Cable Size:
Motor (mm
2
/AWG
2)
)
8 x 300 MCM (8 x 150)
12 x 300 MCM (12 x 150)
Mains (mm
2
/AWG
2)
)
8 x 500 MCM (8 x 250)
Regeneration terminals (mm
2
/AWG
2)
) 4 x 250 MCM (4 x 120)
Brake (mm
2
/AWG
2)
)
4 x 350 MCM (4 x 185)
Estimated Power loss at 690 V AC at
rated max. load (W)
3)
4974 5623 7018 7793 8933 10310 11692 12909 15358 17602
Estimated Power loss at 575 V AC at
rated max. load (W)
3)
5128 5794 7221 8017 9212 10659 12080 13305 15865 18173
Weight Enclosure IP21 kg (lb)
440/656 (880/1443) 880/1096 (1936/2471) 1022/1238 (2248/2724)
Weight enclosure IP 54 kg (lb)
Efficiency
4)
0.98
Output Frequency 0-525 Hz
Heatsink overtemp trip 110 °C 95 °C 105 °C 95 °C 95 °C 105 °C 95 °C
Power card ambient trip 85 °C
Table 8.8 Mains Supply 525-690 V AC
1) For type of fuse, consult the Operating Instructions
2) American Wire Gauge
3) The typical power loss is at normal conditions and expected to be within ± 15% (tolerance relates to variety in voltage and cable conditions.)
These values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors add to the power loss in the frequency
converter and the opposite is also true. If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical
control card power consumptions are included. Further options and customer load can add up to 30 W to the losses (though typically only 4 W
extra for a fully loaded control card or options for slot A or slot B, each)
4) Measured using 5 m screened motor cables at rated load and rated frequency