Specifications

Frame size Description Maximum weight [kg] ([lbs.])
D5h D1h ratings+disconnect and/or brake chopper 166 (255)
D6h D1h ratings+contactor and/or circuit breaker 129 (285)
D7h D2h ratings+disconnect and/or brake chopper 200 (440)
D8h D2h ratings+contactor and/or circuit breaker 225 (496)
Table 8.6 D5h–D8h Weights
8.1.3 12-Pulse Specifications
Mains Supply 380-480 V AC
P315 P355 P400 P450 P500 P560 P630 P710 P800 P1M0
Normal overload 110% for 1 Minute
NO NO NO NO NO NO NO NO NO NO
Typical Shaft Output [kW] at 400 V 315 355 400 450 500 560 630 710 800 1000
Typical Shaft Output [HP] at 460 V 450 500 550/600 600 650 750 900 1000 1200 1350
IP 21/ NEMA 1 F8/F9 F10/F11 F12/F13
IP 54 / NEMA 12 F8/F9 F10/F11 F12/F13
Output Current
Continuous (at 380-440 V) 600 658 745 800 880 990 1120 1260 1460 1720
Intermittent (60 second overload at
380-440 V) 660 724 820 880 968 1089 1232 1386 1606 1892
Continuous (at 400 V) 416 456 516 554 610 686 776 873 1,012 1,192
Intermittent (60 second overload at
460-500 V) 457 501 568 610 671 754 854 960 1,113 1,311
Continuous (at 441–500 V) 540 590 678 730 780 890 1,050 1,160 1,380 1,530
Intermittent (60 second overload) (at
441–500 V) 594 649 746 803 858 979 1,155 1,276 1,518 1,683
Continuous (at 460 V) 430 470 540 582 621 709 837 924 1,100 1,219
Continuous (at 500 V) 473 517 594 640 684 780 920 1,017 1,209 1,341
Max Input Current
Continuous (3x380-440v) [A] 590 647 733 787 857 964 1,090 1,227 1,422 1,675
Continuous (3x441-480v) [A] 531 580 667 718 759 867 1,022 1,129 1,344 1,490
Max. external mains fuses
1)
700 700 700 700 900 900 900 1,500 1,500 1,500
Max Cable Size:
Motor (mm
2
/AWG
2)
)
8 x 300 MCM (8 x 150)
12 x 300 MCM (8
x 150)
Mains (mm
2
/AWG
2)
)
8 x 500 MCM (8 x 250)
Regeneration terminals (mm
2
/AWG
2)
) 4 x 250 MCM (4 x 120)
Brake (mm
2
/AWG
2)
)
2 x 350 MCM (2 x 185) 4 x 350 MCM (4 x 185)
Estimated Power loss at 400 V AC at
rated max. load (W)
3)
6705 7532 8677 9473 10162 11822 12512 14674 17293 19278
Estimated Power loss at 460 V AC at
rated max. load (W)
3)
6705 6724 7819 8527 8876 10424 11595 13213 16229 16624
F9/F11/F13 Max. additional losses for
A1, RFI, CB or disconnect & contactor
682 766 882 963 1054 1093 1230 2280 2236 2541
Weight Enclosure IP21 kg (lb)
263
(580)
270
(595)
272
(600)
313
(690)
1004 (2214) 1246 (2748)
Weight enclosure IP 54 kg (lb)
Efficiency
4)
0.98
Output Frequency 0-590 Hz
Heatsink overtemp. trip 110 °C 95 °C
Power card ambient trip 85 °C
Table 8.7 Mains Supply 380-480 V AC
General Specifications and ... VLT® HVAC Drive FC 102 Design Guide
188 MG16C102 - Rev. 2013-08-20