Specifications

N250 N315 N400 P450 P500 P560
Normal Overload NO NO NO NO NO NO
Typical Shaft output at 550 V [kW] 200 250 315 355 400 450
Typical Shaft output at 575 V [hp] 300 350 400 450 500 600
Typical Shaft output at 690 V [kW] 250 315 400 450 500 560
Enclosure IP00 E2 E2 E2
Enclosure IP20 D4h D4h D4h
Enclosure IP21 D2h D2h D2h E1 E1 E1
Enclosure IP54 D2h D2h D2h E1 E1 E1
Output current
Continuous (at 550 V) [A] 303 360 418 470 523 596
Intermittent (60 s overload) (at 550 V)[A] 333 396 460 517 575 656
Continuous (at 575/690 V) [A] 290 344 400 450 500 570
Intermittent (60 s overload) (at 575/690 V)
[kVA]
319 378 440 495 550 627
Continuous kVA (at 550 V) [kVA] 289 343 398 448 498 568
Continuous kVA (at 575 V) [kVA] 289 343 398 448 498 568
Continuous kVA (at 690 V) [kVA] 347 411 478 538 598 681
Max. Input current
Continuous (at 550 V) [A] 299 355 408 453 504 574
Continuous (at 575 V) [A] 286 339 390 434 482 549
Continuous (at 690 V) [A] 296 352 400 434 482 549
Max. cable size: mains, motor, brake, and
load share (mm
2
/ AWG
2)
)
2x185 (2x350 mcm)
Max. external mains fuses [A] 400 500 550 700 700 900
Estimated power loss at 575 V [W]
3)
3,719 4,460 5,023 5,323 6,010 7,395
Estimated power loss at 690 V [W]
3)
3,848 4,610 5,150 5,529 6,239 7,653
Weight, enclosure IP20, IP21, IP54 kg (lbs.) 125 (275)
Efficiency
4)
0.98
Output frequency [Hz] 0–590 0–525
Heatsink overtemp. trip [°C] 110 95
Power card ambient trip [°C] 80 85
Table 8.4 Mains Supply 3x525-690 V AC
General Specifications and ... VLT® HVAC Drive FC 102 Design Guide
186 MG16C102 - Rev. 2013-08-20
8
8