Specifications
8 General Specifications and Troubleshooting
8.1 General Specifications
8.1.1 Mains Supply 3x380-480 V AC
N110 N132 N160 N200 N250 N315 P355 P400
Normal Overload =110% current
for 60 seconds
NO NO NO NO NO NO NO NO
Typical Shaft output at 400 V
[kW]
110 132 160 200 250 315 355 400
Typical Shaft output at 460 V [hp] 150 200 250 300 350 450 500 550
Enclosure IP00 E2 E2
Enclosure IP20 D3h D3h D3h D4h D4h D4h
Enclosure IP21/NEMA 1 D1h D1h D1h D2h D2h D2h E1 E1
Enclosure IP54/NEMA 12 D1h D1h D1h D2h D2h D2h E1 E1
Output current
Continuous (at 3x380-440 V) [A] 212 260 315 395 480 588 658 745
Intermittent (at 3x380-440 V) [A] 233 286 347 435 528 647 724 820
Continuous (at 3x441-480 V) [A] 190 240 302 361 443 535 590 678
Intermittent (at 3x441-480 V) [A] 209 264 332 397 487 588 649 746
Continuous kVA (at 400 V AC)
[kVA]
147 180 218 274 333 407 456 516
Continuous kVA (at 460 V AC)
[kVA]
151 191 241 288 353 426 470 540
Max. Input current
Continuous (3x380-440 V) [A] 204 251 304 381 463 567 647 733
Continuous (3x441-480 V) [A] 183 231 291 348 427 516 580 667
Max. pre-fuses
1)
[A]
315 350 400 550 630 800 900 900
Max. cable size
Motor (mm
2
/AWG
2) 5)
)
2 x 95
2 x 3/0
2 x 185
2 x 350 mcm
4 x 240
4 x 500 mcm
Mains (mm
2
/AWG
2) 5)
)
Loadsharing (mm
2
/AWG
2) 5)
)
Brake (mm
2
/AWG
2) 5)
)
2 x 185
2 x 350 mcm
Estimated power loss at 400 V AC
at rated max load [W]
3)
2555 2949 3764 4109 5129 6663 7532 8677
Estimated power loss at 460 V AC
at rated max load [W]
3)
2557 2719 3612 3561 4558 5703 6724 7819
Weight, enclosure IP00/IP20 kg
(lbs.)
62 [135] 125 [275]
234
[515]
236 [519]
Weight, enclosure IP21 kg (lbs.)
270
[594]
272 [598]
Weight, enclosure IP54 kg (lbs.)
Efficiency
4)
0.98
Output frequency [Hz] 0–590
Heatsink overtemp. trip [°C] 110
Power card ambient trip [°C] 75 85
Table 8.1 Mains Supply 3x380-480 V AC
General Specifications and ... VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 183
8
8