Specifications
Bit Bit = 0 Bit = 1
00 Control not ready Control ready
01 Drive not ready Drive ready
02 Coasting Enable
03 No error Trip
04 No error Error (no trip)
05 Reserved -
06 No error Triplock
07 No warning Warning
08 Speed ≠ reference Speed = reference
09 Local operation Bus control
10 Out of frequency limit Frequency limit OK
11 No operation In operation
12 Drive OK Stopped, auto start
13 Voltage OK Voltage exceeded
14 Torque OK Torque exceeded
15 Timer OK Timer exceeded
Table 7.37 Status Bits
Explanation of the Status Bits
Bit 00, Control not ready/ready:
Bit 00 = ’0’: The frequency converter trips. Bit 00 = ’1’: The
frequency converter controls are ready but the power
component does not necessarily receive any power supply
(in case of external 24 V supply to controls).
Bit 01, Drive ready:
Bit 01=’1’: The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop:
Bit 02=’0’: The frequency converter releases the motor. Bit
02 = ’1’: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip:
Bit 03=’0’ : The frequency converter is not in fault mode.
Bit 03 = ’1’: The frequency converter trips. To re-establish
operation, enter [Reset].
Bit 04, No error/error (no trip):
Bit 04=’0’: The frequency converter is not in fault mode. Bit
04 = “1”: The frequency converter shows an error but does
not trip.
Bit 05, Not used:
Bit 05 is not used in the status word.
Bit 06, No error/triplock:
Bit 06=’0’: The frequency converter is not in fault mode. Bit
06 = “1”: The frequency converter is tripped and locked.
Bit 07, No warning/warning:
Bit 07=’0’: There are no warnings. Bit 07 = ’1’: A warning
has occurred.
Bit 08, Speed ≠ reference/speed = reference:
Bit 08=’0’: The motor is running but the present speed is
different from the preset speed reference. This can occur
when the speed ramps up/down during start/stop. Bit 08
= ’1’: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control:
Bit 09=’0’: [STOP/RESET] is activated on the control unit or
Local control in F-02 Operation Method is selected. It is
impossible to control the frequency converter via serial
communication. Bit 09 = ’1’ It is possible to control the
frequency converter via the fieldbus/serial communication.
Bit 10, Out of frequency limit:
Bit 10=’0’: The output frequency has reached the value in
F-18 Motor Speed Low Limit [RPM] or F-17 Motor Speed High
Limit [RPM]. Bit 10 = "1": The output frequency is within
the defined limits.