Specifications

6.1.11 Fixed Variable Speed Pump Wiring
Diagram
L1/L2/L3 L1/L2/L3 L1/L2/L3
Power Section
RELAY 1
RELAY 2
130BA376.10
Illustration 6.9 Fixed Variable Speed Pump Wiring Diagram
6.1.12 Lead Pump Alternation Wiring
Diagram
130BA377.13
L1/L2/L3
FC
L1/L2/L3
L1/L2/L3
k3
k2
k3
k1
K2
K1
K1
K1
K4
K3
K4
K3
R1
R2
Illustration 6.10 Lead Pump Alternation Wiring Diagram
Every pump must be connected to 2 contactors (K1/K2 and
K3/K4) with a mechanical interlock. Apply thermal relays or
other motor protection devices according to local
regulation and/or individual demands.
Relay 1 (R1) and Relay 2 (R2) are the built-in
relays in the frequency converter.
When all relays are de-energised, the first built in
relay to be energised cuts in the contactor
corresponding to the pump controlled by the
relay.
K1 blocks for K2 via the mechanical interlock
preventing mains to be connected to the output
of the frequency converter (via K1).
Auxiliary break contact on K1 prevents K3 to cut
in.
RELAY 2 controls contactor K4 for on/off control
of the fixed speed pump.
At alternation both relays de-energise and now
Relay 2 is energised as the first relay.
Application Examples VLT® HVAC Drive FC 102 Design Guide
160 MG16C102 - Rev. 2013-08-20