Specifications
6 Application Examples
6.1 Application Examples
6.1.1 Start/Stop
Terminal 18 = start/stop E-01 Terminal 18 Digital Input [8]
Start
Terminal 27 = No operation E-03 Terminal 27 Digital Input
[0] No operation (Default coast inverse)
E-01 Terminal 18 Digital Input = Start (default)
E-03 Terminal 27 Digital Input = coast inverse
(default)
12 13 18 37
130BA155.12
322719293320
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Illustration 6.1 Terminal 37: Available only with STO Function
6.1.2 Pulse Start/Stop
Terminal 18 = start/stop E-01 Terminal 18 Digital Input [9]
Latched start
Terminal 27= Stop E-03 Terminal 27 Digital Input [6] Stop
inverse
E-01 Terminal 18 Digital Input = Latched start
E-03 Terminal 27 Digital Input = Stop inverse
12 13 18 37
130BA156.12
32271929 3320
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start Stop inverse Safe Stop
Start (18)
Start (27)
Illustration 6.2 Terminal 37: Available only with STO Function
6.1.3 Potentiometer Reference
Voltage reference via a potentiometer.
F-01 Frequency Setting 1 [1] = Analogue Input 53
AN-10 Terminal 53 Low Voltage = 0 V
AN-11 Terminal 53 High Voltage = 10 V
AN-14 Terminal 53 Low Ref./Feedb. Value = 0 RPM
AN-15 Terminal 53 High Ref./Feedb. Value = 1.500
RPM
Switch S201 = OFF (U)
130BA287.10
555039 425354
Speed RPM
P 6-15
1 kW
+10V/30mA
Ref. voltage
P 6-11 10V
Illustration 6.3 Potentiometer Voltage Reference
Application Examples VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 155