Specifications

5.4.2 Circuit Breakers
Default breaker settings (Trip level -
Amps)
Frame Size Voltage [V] Drive Model Circuit Breaker Type I1 (Overload) I3/Ith (Instantaneous)
D6h 380-480 N110 - N132 ABB T5L400TW 400 4000
D6h 380-480 N160 ABB T5LQ400TW 400 4000
D8h 380-480 N200 ABB T6L600TW 600 6000
D8h 380-480 N250 ABB T6LQ600TW 600 6000
D8h 380-480 N315 ABB T6LQ800TW 800 8000
D6h 525-690 N75K - N160 ABB T5L400TW 400 4000
D8h 525-690 N200 - N315 ABB T6L600TW 600 6000
D8h 525-690 N400 ABB T6LQ600TW 600 6000
Table 5.75 D-frame Circuit Breakers
Frame size Power & Voltage Type Default breaker settings
Trip level [A] Time [s]
F3
P450 380-500 V & P630-P710
525-690 V Merlin Gerin NPJF36120U31AABSCYP 1200 0.5
F3
P500-P630 380-500 V & P800
525-690 V Merlin Gerin NRJF36200U31AABSCYP 2000 0.5
F4
P710 380-500 V & P900-P1M2
525-690 V Merlin Gerin NRJF36200U31AABSCYP 2000 0.5
F4 P800 380-500 V Merlin Gerin NRJF36250U31AABSCYP 2500 0.5
Table 5.76 F-frame Circuit Breakers
5.4.3 Mains Contactors
Frame size Power & Voltage Contactor
D6h
N90K-N132 380-500 V GE CK95CE311N
N110-N160 380-480 V GE CK95BE311N
N55-N132 525-690 V GE CK95CE311N
N75-N160 525-690 V GE CK95BE311N
D8h
N160-N250 380-500 V
GE CK11CE311N
N200-N315 380-480 V
N160-N315 525-690 V
N200-N400 525-690 V
Table 5.77 D-frame Contactors
Frame size Power & Voltage Contactor
F3 P450-P500 380-500 V & P630-P800 525-690 V Eaton XTCE650N22A
F3 P560 380-500 V Eaton XTCE820N22A
F3 P630 380-500 V Eaton XTCEC14P22B
F4 P900 525-690 V Eaton XTCE820N22A
F4 P710-P800 380-500 V & P1M2 525-690 V Eaton XTCEC14P22B
Table 5.78 F-frame Contactors
NOTICE
Customer-supplied 230 V supply is required for mains contactors.
How to Install VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 145
5
5