Specifications
5.4 Additional Connections
5.4.1 Mains Disconnects
Frame size Power Type
380-500 V
D5h/D6h N110-N160 ABB OT400U03
D7h/D8h N200-N400 ABB OT600U03
E1/E2 P250 ABB OETL-NF600A
E1/E2 P315-P400 ABB OETL-NF800A
F3 P450 Merlin Gerin NPJF36000S12AAYP
F3 P500-P630 Merlin Gerin NRKF36000S20AAYP
F4 P710-P800 Merlin Gerin NRKF36000S20AAYP
525-690 V
D5h/D6h N75K-N160 ABB OT400U03
D5h/D6h N200-N400 ABB OT600U03
F3 P630-P710 Merlin Gerin NPJF36000S12AAYP
F3 P800 Merlin Gerin NRKF36000S20AAYP
F4 P900-P1M2 Merlin Gerin NRKF36000S20AAYP
Table 5.73 Mains Disconnects, D, E and F- frame Frequency Converters
Frame size Power Type
380-500 V
F9 P250 ABB OETL-NF600A
F9 P315 ABB OETL-NF600A
F9 P355 ABB OETL-NF600A
F9 P400 ABB OETL-NF600A
F11 P450 ABB OETL-NF800A
F11 P500 ABB OETL-NF800A
F11 P560 ABB OETL-NF800A
F11 P630 ABB OT800U21
F13 P710 Merlin Gerin NPJF36000S12AAYP
F13 P800 Merlin Gerin NPJF36000S12AAYP
525-690 V
F9 P355 ABB OT400U12-121
F9 P400 ABB OT400U12-121
F9 P500 ABB OT400U12-121
F9 P560 ABB OT400U12-121
F11 P630 ABB OETL-NF600A
F11 P710 ABB OETL-NF600A
F11 P800 ABB OT800U21
F13 P900 ABB OT800U21
F13 P1M0 Merlin Gerin NPJF36000S12AAYP
F13 P1M2 Merlin Gerin NPJF36000S12AAYP
Table 5.74 Mains Disconnects, 12-Pulse Frequency Converters
How to Install VLT® HVAC Drive FC 102 Design Guide
144 MG16C102 - Rev. 2013-08-20
5
5