3. Perform an Automatic Motor Adaptation (AMA) to
ensure optimum performance.
a. Connect terminal 27 to terminal 12 or set
E-03 Terminal 27 Digital Input to 'No function'
(E-03 Terminal 27 Digital Input [0]).
b.
Activate the AMA P-04 Auto Tune.
c. Choose between complete or reduced AMA. If an
LC filter is mounted, run only the reduced AMA,
or remove the LC filter during the AMA
procedure.
d. Press [OK]. The display shows “Press [Hand On] to
start.”
e. Press [Hand On]. A progress bar indicates if the
AMA is in progress.
f. Press [OFF] - the frequency converter enters into
alarm mode and the display shows that the AMA
was terminated by the user.
Stop the AMA during operation
Successful AMA
•
The display shows “Press [OK] to finish AMA”.
•
Press [OK] to exit the AMA state.
Unsuccessful AMA
•
The frequency converter enters into alarm mode.
A description of the alarm can be found in
8.6 Troubleshooting.
•
"Report Value” in the alarm log shows the last
measuring sequence carried out by the AMA,
before the frequency converter entered alarm
mode. This number, along with the description of
the alarm, will assist in troubleshooting. Mention
the number and alarm description when
contacting Danfoss service personnel.
Unsuccessful AMA is often caused by incorrectly registered
motor name plate data or too big a difference between
the motor power size and the frequency converter power
size.
Set up the desired limits for speed and ramp time.
Minimum Reference
F-52 Minimum Reference
Maximum Reference
F-53 Maximum Reference
Table 5.70 Reference Parameters
Motor Speed Low Limit
F-18 Motor Speed Low Limit
[RPM] or F-16 Motor Speed Low
Limit [Hz]
Motor Speed High Limit
F-17 Motor Speed High Limit
[RPM] or F-15 Motor Speed High
Limit [Hz]
Table 5.71 Speed Limits
Ramp-up Time 1 [s]
F-07 Accel Time 1
Ramp-down Time 1 [s]
F-08 Decel Time 1
Table 5.72 Ramp Times
How to Install VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 143
5