Specifications
Input polarity of control terminals
12 13 18 1927 29 32 33 20 37
+24 VDC
0 VDC
130BT106.10
PNP (Source)
Digital input wiring
Illustration 5.93 Input Polarity of Control Terminals, PNP
NPN (Sink)
Digital input wiring
12 13 18 1927 29 32 33 20 37
+24 VDC
0 VDC
130BT107.11
Illustration 5.94 Input Polarity of Control Terminals, NPN
5.2.16 Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used to select a
current (0-20 mA) or a voltage (0 to 10 V) configuration of
the analogue input terminals 53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination
on the RS-485 port (terminals 68 and 69).
See
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NOTICE
Change the switch position at power off only.
130BT310.11
Illustration 5.95 Switch Location
5.3 Final Set-Up and Test
Before operating the frequency converter, perform a final
test of the installation:
1. Locate the motor name plate to find out whether
the motor is star- (Y) or delta- connected (Δ).
2. Enter the motor name plate data in the
parameter list. Access the list by pressing the
[QUICK MENU] key and selecting Q2 Quick Setup.
See Table 5.69.
1. Motor Power [kW]
or Motor Power [HP]
P-07 Motor Power [kW]
P-02 Motor Power [HP]
2. Motor Voltage
F-05 Motor Rated Voltage
3. Motor Frequency
F-04 Base Frequency
4. Motor Current
P-03 Motor Current
5. Motor Nominal Speed
P-06 Base Speed
Table 5.69 Quick Setup Parameters
How to Install VLT® HVAC Drive FC 102 Design Guide
142 MG16C102 - Rev. 2013-08-20