Specifications

Enclosure
size
Power
[kW]
Recommended
fuse size
Recommended
Max. fuse
D
N75K
aR-160 aR-160
N90K-N160 aR-160 aR-160
N200-N400 aR-550 aR-550
E
P450-P500T7 aR-700 aR-700
P560-P630T7 aR-900 (500-560) aR-900 (500-560)
F
P710-P1M0T7
aR-1600 aR-1600
P1M2T7
aR-2000 aR-2000
P1M4T7
aR-2500 aR-2500
Table 5.66 525-690 V, Fuse Recommendations, Frame Sizes D, E and F
5.2.11 Control Terminals
1
4
2
3
130BA012.12
61
68
69
39
42
50
53
54
55
12
13
18
19
27
29
32
33
20
37
Illustration 5.83 Control Terminals (all Enclosures)
1 10-pole plug digital I/O
2 3-pole plug RS-485 Bus
3 6-pole analogue I/O
4 USB Connection
Table 5.67 Legend to Illustration 5.83
5.2.12 Control Cable Terminals
To mount the cable to the terminal:
1. Strip isolation of 9-10 mm.
2. Insert a screw driver (Max. 0.4 x 2.5 mm) in the
rectangular hole.
3. Insert the cable in the adjacent circular hole.
4. Remove the screw driver. The cable is now
mounted to the terminal.
Control cable torque value is 0.5-0.6 Nm (5 in-lbs.)
To remove the cable from the terminal:
1.
Insert a screw driver
1)
in the square hole.
2. Pull out the cable.
Wiring to Control Terminals
130BA150.10
9 - 10 mm
(0.37 in)
Illustration 5.84 Strip Isolation
130BT312.10
Illustration 5.85 Insert Screwdriver and Cable
How to Install VLT® HVAC Drive FC 102 Design Guide
MG16C102 - Rev. 2013-08-20 135